⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 120 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 3.34V (2.78%)
Voltage at Load End116.8 VLoss: 3.22 V (354.1 W)
Power & Breaker (125%)13.2 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 120 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A82.79 V (68.99%)37.2 V136.56 V (113.8%)9106.7 WDrop/Amp High
12 AWG3.31 mm²20 A52.02 V (43.35%)68.0 V85.82 V (71.51%)5722.7 WDrop/Amp High
10 AWG5.26 mm²30 A32.74 V (27.28%)87.3 V54.0 V (45.0%)3601.1 WDrop/Amp High
8 AWG8.37 mm²50 A20.57 V (17.14%)99.4 V33.94 V (28.28%)2263.1 WDrop/Amp High
6 AWG13.3 mm²65 A12.95 V (10.79%)107.1 V21.36 V (17.8%)1424.2 WDrop/Amp High
4 AWG21.15 mm²85 A8.14 V (6.78%)111.9 V13.43 V (11.19%)895.6 WDrop/Amp High
3 AWG26.67 mm²100 A6.46 V (5.38%)113.5 V10.65 V (8.88%)710.2 WDrop/Amp High
2 AWG33.62 mm²115 A5.12 V (4.27%)114.9 V8.45 V (7.04%)563.4 W~ ≤5%
1 AWG42.41 mm²130 A4.06 V (3.38%)115.9 V6.7 V (5.58%)446.6 W~ ≤5%
1/0 AWG53.49 mm²150 A3.22 V (2.68%)116.8 V5.31 V (4.43%)354.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.55 V (2.13%)117.4 V4.21 V (3.51%)280.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.03 V (1.69%)118.0 V3.34 V (2.78%)222.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.61 V (1.34%)118.4 V2.65 V (2.21%)176.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.36 V (1.13%)118.6 V2.24 V (1.87%)149.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.13 V (0.94%)118.9 V1.87 V (1.56%)124.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.97 V (0.81%)119.0 V1.6 V (1.34%)106.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.85 V (0.71%)119.2 V1.4 V (1.17%)93.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.68 V (0.57%)119.3 V1.12 V (0.93%)74.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.57 V (0.47%)119.4 V0.93 V (0.78%)62.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.45 V (0.38%)119.5 V0.75 V (0.62%)49.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.34 V (0.28%)119.7 V0.56 V (0.47%)37.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 120 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 120 feet one-way at 120V (1-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 3.22V (2.68%) and delivers 116.8V at the load.

What size aluminum wire is required for 110 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 3.34V (2.78%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.