⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 125 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 3.48V (2.9%)
Voltage at Load End116.6 VLoss: 3.35 V (368.9 W)
Power & Breaker (125%)13.2 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 125 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A86.24 V (71.86%)33.8 V142.25 V (118.54%)9486.2 WDrop/Amp High
12 AWG3.31 mm²20 A54.19 V (45.16%)65.8 V89.39 V (74.49%)5961.1 WDrop/Amp High
10 AWG5.26 mm²30 A34.1 V (28.42%)85.9 V56.25 V (46.88%)3751.2 WDrop/Amp High
8 AWG8.37 mm²50 A21.43 V (17.86%)98.6 V35.35 V (29.46%)2357.4 WDrop/Amp High
6 AWG13.3 mm²65 A13.49 V (11.24%)106.5 V22.25 V (18.54%)1483.6 WDrop/Amp High
4 AWG21.15 mm²85 A8.48 V (7.07%)111.5 V13.99 V (11.66%)932.9 WDrop/Amp High
3 AWG26.67 mm²100 A6.73 V (5.6%)113.3 V11.09 V (9.25%)739.8 WDrop/Amp High
2 AWG33.62 mm²115 A5.34 V (4.45%)114.7 V8.8 V (7.33%)586.9 W~ ≤5%
1 AWG42.41 mm²130 A4.23 V (3.52%)115.8 V6.98 V (5.81%)465.2 W~ ≤5%
1/0 AWG53.49 mm²150 A3.35 V (2.79%)116.6 V5.53 V (4.61%)368.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.66 V (2.22%)117.3 V4.39 V (3.66%)292.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.11 V (1.76%)117.9 V3.48 V (2.9%)232.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.67 V (1.39%)118.3 V2.76 V (2.3%)184.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.42 V (1.18%)118.6 V2.34 V (1.95%)155.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.18 V (0.98%)118.8 V1.95 V (1.62%)129.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.01 V (0.84%)119.0 V1.67 V (1.39%)111.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.88 V (0.74%)119.1 V1.46 V (1.22%)97.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.71 V (0.59%)119.3 V1.17 V (0.97%)77.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.59 V (0.49%)119.4 V0.97 V (0.81%)64.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.47 V (0.39%)119.5 V0.78 V (0.65%)51.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.35 V (0.3%)119.6 V0.58 V (0.49%)38.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 125 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 125 feet one-way at 120V (1-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 3.35V (2.79%) and delivers 116.6V at the load.

What size aluminum wire is required for 110 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 3.48V (2.9%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.