🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 40 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 1.42%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 1.77V (1.48%)
Voltage at Load End118.3 VLoss: 1.71 V (187.8 W)
Power & Breaker (125%)13.2 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 40 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A27.6 V (23.0%)92.4 V45.52 V (37.93%)3035.6 WDrop/Amp High
12 AWG3.31 mm²20 A17.34 V (14.45%)102.7 V28.61 V (23.84%)1907.6 WDrop/Amp High
10 AWG5.26 mm²30 A10.91 V (9.09%)109.1 V18.0 V (15.0%)1200.4 WDrop/Amp High
8 AWG8.37 mm²50 A6.86 V (5.71%)113.1 V11.31 V (9.43%)754.4 WDrop/Amp High
6 AWG13.3 mm²65 A4.32 V (3.6%)115.7 V7.12 V (5.93%)474.7 WDrop/Amp High
4 AWG21.15 mm²85 A2.71 V (2.26%)117.3 V4.48 V (3.73%)298.5 WDrop/Amp High
3 AWG26.67 mm²100 A2.15 V (1.79%)117.8 V3.55 V (2.96%)236.7 WDrop/Amp High
2 AWG33.62 mm²115 A1.71 V (1.42%)118.3 V2.82 V (2.35%)187.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.35 V (1.13%)118.6 V2.23 V (1.86%)148.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.07 V (0.89%)118.9 V1.77 V (1.48%)118.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.85 V (0.71%)119.1 V1.4 V (1.17%)93.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.68 V (0.56%)119.3 V1.11 V (0.93%)74.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.54 V (0.45%)119.5 V0.88 V (0.74%)58.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.45 V (0.38%)119.5 V0.75 V (0.62%)49.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.38 V (0.31%)119.6 V0.62 V (0.52%)41.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.32 V (0.27%)119.7 V0.53 V (0.45%)35.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.28 V (0.24%)119.7 V0.47 V (0.39%)31.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.23 V (0.19%)119.8 V0.37 V (0.31%)24.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.19 V (0.16%)119.8 V0.31 V (0.26%)20.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.15 V (0.13%)119.8 V0.25 V (0.21%)16.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.11 V (0.09%)119.9 V0.19 V (0.16%)12.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 40 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 40 feet one-way at 120V (1-Phase), you need 2 AWG copper wire. This produces a voltage drop of 1.71V (1.42%) and delivers 118.3V at the load.

What size aluminum wire is required for 110 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 1.77V (1.48%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.