🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 300 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.66%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 6.62V (2.76%)
Voltage at Load End233.6 VLoss: 6.38 V (702.3 W)
Power & Breaker (125%)26.4 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 300 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A206.97 V (86.24%)33.0 V341.41 V (142.25%)22766.8 WDrop/Amp High
12 AWG3.31 mm²20 A130.06 V (54.19%)109.9 V214.54 V (89.39%)14306.6 WDrop/Amp High
10 AWG5.26 mm²30 A81.84 V (34.1%)158.2 V135.0 V (56.25%)9002.8 WDrop/Amp High
8 AWG8.37 mm²50 A51.43 V (21.43%)188.6 V84.84 V (35.35%)5657.7 WDrop/Amp High
6 AWG13.3 mm²65 A32.37 V (13.49%)207.6 V53.39 V (22.25%)3560.5 WDrop/Amp High
4 AWG21.15 mm²85 A20.35 V (8.48%)219.6 V33.58 V (13.99%)2239.0 WDrop/Amp High
3 AWG26.67 mm²100 A16.14 V (6.73%)223.9 V26.63 V (11.09%)1775.6 WDrop/Amp High
2 AWG33.62 mm²115 A12.8 V (5.34%)227.2 V21.12 V (8.8%)1408.5 WDrop/Amp High
1 AWG42.41 mm²130 A10.15 V (4.23%)229.8 V16.74 V (6.98%)1116.6 W~ ≤5%
1/0 AWG53.49 mm²150 A8.05 V (3.35%)232.0 V13.28 V (5.53%)885.3 W~ ≤5%
2/0 AWG67.43 mm²175 A6.38 V (2.66%)233.6 V10.53 V (4.39%)702.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A5.06 V (2.11%)234.9 V8.35 V (3.48%)557.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A4.02 V (1.67%)236.0 V6.62 V (2.76%)441.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.4 V (1.42%)236.6 V5.6 V (2.34%)373.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.83 V (1.18%)237.2 V4.67 V (1.95%)311.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.43 V (1.01%)237.6 V4.01 V (1.67%)267.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.12 V (0.88%)237.9 V3.5 V (1.46%)233.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.7 V (0.71%)238.3 V2.8 V (1.17%)186.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.42 V (0.59%)238.6 V2.34 V (0.97%)155.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.13 V (0.47%)238.9 V1.87 V (0.78%)124.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.85 V (0.35%)239.2 V1.4 V (0.58%)93.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 300 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 300 feet one-way at 240V (1-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 6.38V (2.66%) and delivers 233.6V at the load.

What size aluminum wire is required for 110 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 6.62V (2.76%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.