🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 75 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 1.33%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 3.32V (1.38%)
Voltage at Load End236.8 VLoss: 3.2 V (352.1 W)
Power & Breaker (125%)26.4 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A51.74 V (21.56%)188.3 V85.35 V (35.56%)5691.7 WDrop/Amp High
12 AWG3.31 mm²20 A32.52 V (13.55%)207.5 V53.63 V (22.35%)3576.7 WDrop/Amp High
10 AWG5.26 mm²30 A20.46 V (8.53%)219.5 V33.75 V (14.06%)2250.7 WDrop/Amp High
8 AWG8.37 mm²50 A12.86 V (5.36%)227.1 V21.21 V (8.84%)1414.4 WDrop/Amp High
6 AWG13.3 mm²65 A8.09 V (3.37%)231.9 V13.35 V (5.56%)890.1 WDrop/Amp High
4 AWG21.15 mm²85 A5.09 V (2.12%)234.9 V8.39 V (3.5%)559.8 WDrop/Amp High
3 AWG26.67 mm²100 A4.04 V (1.68%)236.0 V6.66 V (2.77%)443.9 WDrop/Amp High
2 AWG33.62 mm²115 A3.2 V (1.33%)236.8 V5.28 V (2.2%)352.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.54 V (1.06%)237.5 V4.19 V (1.74%)279.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.01 V (0.84%)238.0 V3.32 V (1.38%)221.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.6 V (0.67%)238.4 V2.63 V (1.1%)175.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.27 V (0.53%)238.7 V2.09 V (0.87%)139.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.0 V (0.42%)239.0 V1.66 V (0.69%)110.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.85 V (0.35%)239.2 V1.4 V (0.58%)93.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.71 V (0.3%)239.3 V1.17 V (0.49%)77.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.61 V (0.25%)239.4 V1.0 V (0.42%)66.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.53 V (0.22%)239.5 V0.88 V (0.36%)58.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.42 V (0.18%)239.6 V0.7 V (0.29%)46.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.35 V (0.15%)239.6 V0.58 V (0.24%)38.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.28 V (0.12%)239.7 V0.47 V (0.19%)31.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.21 V (0.09%)239.8 V0.35 V (0.15%)23.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 75 feet one-way at 240V (1-Phase), you need 2 AWG copper wire. This produces a voltage drop of 3.2V (1.33%) and delivers 236.8V at the load.

What size aluminum wire is required for 110 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 3.32V (1.38%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.