🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 50 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 0.89%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 2.21V (0.92%)
Voltage at Load End237.9 VLoss: 2.13 V (234.8 W)
Power & Breaker (125%)26.4 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 50 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A34.5 V (14.37%)205.5 V56.9 V (23.71%)3794.5 WDrop/Amp High
12 AWG3.31 mm²20 A21.68 V (9.03%)218.3 V35.76 V (14.9%)2384.4 WDrop/Amp High
10 AWG5.26 mm²30 A13.64 V (5.68%)226.4 V22.5 V (9.38%)1500.5 WDrop/Amp High
8 AWG8.37 mm²50 A8.57 V (3.57%)231.4 V14.14 V (5.89%)942.9 WDrop/Amp High
6 AWG13.3 mm²65 A5.39 V (2.25%)234.6 V8.9 V (3.71%)593.4 WDrop/Amp High
4 AWG21.15 mm²85 A3.39 V (1.41%)236.6 V5.6 V (2.33%)373.2 WDrop/Amp High
3 AWG26.67 mm²100 A2.69 V (1.12%)237.3 V4.44 V (1.85%)295.9 WDrop/Amp High
2 AWG33.62 mm²115 A2.13 V (0.89%)237.9 V3.52 V (1.47%)234.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.69 V (0.7%)238.3 V2.79 V (1.16%)186.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.34 V (0.56%)238.7 V2.21 V (0.92%)147.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.06 V (0.44%)238.9 V1.76 V (0.73%)117.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.84 V (0.35%)239.2 V1.39 V (0.58%)92.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.67 V (0.28%)239.3 V1.1 V (0.46%)73.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.57 V (0.24%)239.4 V0.93 V (0.39%)62.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.47 V (0.2%)239.5 V0.78 V (0.32%)51.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.4 V (0.17%)239.6 V0.67 V (0.28%)44.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.35 V (0.15%)239.6 V0.58 V (0.24%)38.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.28 V (0.12%)239.7 V0.47 V (0.19%)31.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.24 V (0.1%)239.8 V0.39 V (0.16%)26.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.19 V (0.08%)239.8 V0.31 V (0.13%)20.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (0.06%)239.9 V0.23 V (0.1%)15.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 50 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 50 feet one-way at 240V (1-Phase), you need 2 AWG copper wire. This produces a voltage drop of 2.13V (0.89%) and delivers 237.9V at the load.

What size aluminum wire is required for 110 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 2.21V (0.92%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.