⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 500 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 6.64V (2.76%)
Voltage at Load End233.6 VLoss: 6.44 V (804.4 W)
Power & Breaker (125%)30.0 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A391.99 V (163.33%)0.0 V646.6 V (269.42%)48998.8 WDrop/Amp High
12 AWG3.31 mm²20 A246.33 V (102.64%)0.0 V406.32 V (169.3%)30790.8 WDrop/Amp High
10 AWG5.26 mm²30 A155.01 V (64.59%)85.0 V255.69 V (106.54%)19376.0 WDrop/Amp High
8 AWG8.37 mm²50 A97.41 V (40.59%)142.6 V160.68 V (66.95%)12176.5 WDrop/Amp High
6 AWG13.3 mm²65 A61.3 V (25.54%)178.7 V101.12 V (42.13%)7663.0 WDrop/Amp High
4 AWG21.15 mm²85 A38.55 V (16.06%)201.4 V63.59 V (26.5%)4818.8 WDrop/Amp High
3 AWG26.67 mm²100 A30.57 V (12.74%)209.4 V50.43 V (21.01%)3821.4 WDrop/Amp High
2 AWG33.62 mm²115 A24.25 V (10.1%)215.7 V40.0 V (16.67%)3031.5 WDrop/Amp High
1 AWG42.41 mm²130 A19.23 V (8.01%)220.8 V31.71 V (13.21%)2403.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.24 V (6.35%)224.8 V25.14 V (10.48%)1905.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.09 V (5.04%)227.9 V19.95 V (8.31%)1511.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.59 V (4.0%)230.4 V15.82 V (6.59%)1198.9 W~ ≤5%
4/0 AWG107.2 mm²230 A7.61 V (3.17%)232.4 V12.55 V (5.23%)950.7 W~ ≤5%
250 kcmil126.7 mm²255 A6.44 V (2.68%)233.6 V10.62 V (4.42%)804.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A5.36 V (2.24%)234.6 V8.85 V (3.69%)670.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.6 V (1.92%)235.4 V7.59 V (3.16%)574.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.02 V (1.68%)236.0 V6.64 V (2.76%)502.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.22 V (1.34%)236.8 V5.31 V (2.21%)402.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.68 V (1.12%)237.3 V4.42 V (1.84%)335.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.15 V (0.89%)237.9 V3.54 V (1.47%)268.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.61 V (0.67%)238.4 V2.65 V (1.11%)201.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 500 feet one-way at 240V (1-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 6.44V (2.68%) and delivers 233.6V at the load.

What size aluminum wire is required for 125 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 6.64V (2.76%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.