🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 500 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.86%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.49V (3.54%)
Voltage at Load End233.1 VLoss: 6.87 V (2746.4 W)
Power & Breaker (125%)96.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1254.37 V (522.65%)0.0 V2069.12 V (862.13%)501747.7 WDrop/Amp High
12 AWG3.31 mm²20 A788.24 V (328.44%)0.0 V1300.23 V (541.76%)315297.6 WDrop/Amp High
10 AWG5.26 mm²30 A496.02 V (206.68%)0.0 V818.21 V (340.92%)198409.7 WDrop/Amp High
8 AWG8.37 mm²50 A311.72 V (129.88%)0.0 V514.19 V (214.25%)124687.6 WDrop/Amp High
6 AWG13.3 mm²65 A196.17 V (81.74%)43.8 V323.59 V (134.83%)78468.8 WDrop/Amp High
4 AWG21.15 mm²85 A123.36 V (51.4%)116.6 V203.49 V (84.79%)49344.5 WDrop/Amp High
3 AWG26.67 mm²100 A97.83 V (40.76%)142.2 V161.37 V (67.24%)39131.4 WDrop/Amp High
2 AWG33.62 mm²115 A77.61 V (32.34%)162.4 V128.01 V (53.34%)31042.1 WDrop/Amp High
1 AWG42.41 mm²130 A61.52 V (25.63%)178.5 V101.48 V (42.28%)24608.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A48.78 V (20.32%)191.2 V80.46 V (33.52%)19510.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A38.69 V (16.12%)201.3 V63.83 V (26.59%)15477.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A30.69 V (12.79%)209.3 V50.63 V (21.09%)12276.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A24.34 V (10.14%)215.7 V40.15 V (16.73%)9735.4 WDrop/Amp High
250 kcmil126.7 mm²255 A20.59 V (8.58%)219.4 V33.97 V (14.15%)8237.1 WDrop/Amp High
300 kcmil152.0 mm²285 A17.17 V (7.15%)222.8 V28.31 V (11.8%)6866.0 WDrop/Amp High
350 kcmil177.3 mm²310 A14.72 V (6.13%)225.3 V24.27 V (10.11%)5886.3 WDrop/Amp High
400 kcmil202.7 mm²335 A12.87 V (5.36%)227.1 V21.23 V (8.85%)5148.7 WDrop/Amp High
500 kcmil253.4 mm²380 A10.3 V (4.29%)229.7 V16.98 V (7.08%)4118.5 WDrop/Amp High
600 kcmil304.0 mm²420 A8.58 V (3.58%)231.4 V14.16 V (5.9%)3433.0 W~ ≤5%
750 kcmil380.0 mm²475 A6.87 V (2.86%)233.1 V11.33 V (4.72%)2746.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A5.15 V (2.15%)234.9 V8.49 V (3.54%)2059.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 500 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 6.87V (2.86%) and delivers 233.1V at the load.

What size aluminum wire is required for 400 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.49V (3.54%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.