100 Amp Wire Size at 500 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 100 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.54%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 7.08V (2.95%)
Voltage at Load End233.9 VLoss: 6.08 V (608.5 W)
Power & Breaker (125%)24.0 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 100 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A313.59 V (130.66%)0.0 V517.28 V (215.53%)31359.2 WDrop/Amp High
12 AWG3.31 mm²20 A197.06 V (82.11%)42.9 V325.06 V (135.44%)19706.1 WDrop/Amp High
10 AWG5.26 mm²30 A124.01 V (51.67%)116.0 V204.55 V (85.23%)12400.6 WDrop/Amp High
8 AWG8.37 mm²50 A77.93 V (32.47%)162.1 V128.55 V (53.56%)7793.0 WDrop/Amp High
6 AWG13.3 mm²65 A49.04 V (20.43%)191.0 V80.9 V (33.71%)4904.3 WDrop/Amp High
4 AWG21.15 mm²85 A30.84 V (12.85%)209.2 V50.87 V (21.2%)3084.0 WDrop/Amp High
3 AWG26.67 mm²100 A24.46 V (10.19%)215.5 V40.34 V (16.81%)2445.7 WDrop/Amp High
2 AWG33.62 mm²115 A19.4 V (8.08%)220.6 V32.0 V (13.33%)1940.1 WDrop/Amp High
1 AWG42.41 mm²130 A15.38 V (6.41%)224.6 V25.37 V (10.57%)1538.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.19 V (5.08%)227.8 V20.11 V (8.38%)1219.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.67 V (4.03%)230.3 V15.96 V (6.65%)967.3 W~ ≤5%
3/0 AWG85.01 mm²200 A7.67 V (3.2%)232.3 V12.66 V (5.27%)767.3 W~ ≤5%
4/0 AWG107.2 mm²230 A6.08 V (2.54%)233.9 V10.04 V (4.18%)608.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A5.15 V (2.15%)234.9 V8.49 V (3.54%)514.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.29 V (1.79%)235.7 V7.08 V (2.95%)429.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.68 V (1.53%)236.3 V6.07 V (2.53%)367.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.22 V (1.34%)236.8 V5.31 V (2.21%)321.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.57 V (1.07%)237.4 V4.25 V (1.77%)257.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.15 V (0.89%)237.9 V3.54 V (1.47%)214.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.72 V (0.72%)238.3 V2.83 V (1.18%)171.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.29 V (0.54%)238.7 V2.12 V (0.88%)128.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 100 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 100A load over 500 feet one-way at 240V (1-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 6.08V (2.54%) and delivers 233.9V at the load.

What size aluminum wire is required for 100 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 7.08V (2.95%).

What breaker size is needed for a 100A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (100A × 1.25 = 125.0A), which corresponds to a standard 125A circuit breaker.