🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 125 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 0.89%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.12V (0.88%)
Voltage at Load End237.9 VLoss: 2.15 V (858.3 W)
Power & Breaker (125%)96.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A313.59 V (130.66%)0.0 V517.28 V (215.53%)125436.9 WDrop/Amp High
12 AWG3.31 mm²20 A197.06 V (82.11%)42.9 V325.06 V (135.44%)78824.4 WDrop/Amp High
10 AWG5.26 mm²30 A124.01 V (51.67%)116.0 V204.55 V (85.23%)49602.4 WDrop/Amp High
8 AWG8.37 mm²50 A77.93 V (32.47%)162.1 V128.55 V (53.56%)31171.9 WDrop/Amp High
6 AWG13.3 mm²65 A49.04 V (20.43%)191.0 V80.9 V (33.71%)19617.2 WDrop/Amp High
4 AWG21.15 mm²85 A30.84 V (12.85%)209.2 V50.87 V (21.2%)12336.1 WDrop/Amp High
3 AWG26.67 mm²100 A24.46 V (10.19%)215.5 V40.34 V (16.81%)9782.9 WDrop/Amp High
2 AWG33.62 mm²115 A19.4 V (8.08%)220.6 V32.0 V (13.33%)7760.5 WDrop/Amp High
1 AWG42.41 mm²130 A15.38 V (6.41%)224.6 V25.37 V (10.57%)6152.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.19 V (5.08%)227.8 V20.11 V (8.38%)4877.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.67 V (4.03%)230.3 V15.96 V (6.65%)3869.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.67 V (3.2%)232.3 V12.66 V (5.27%)3069.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.08 V (2.54%)233.9 V10.04 V (4.18%)2433.9 WDrop/Amp High
250 kcmil126.7 mm²255 A5.15 V (2.15%)234.9 V8.49 V (3.54%)2059.3 WDrop/Amp High
300 kcmil152.0 mm²285 A4.29 V (1.79%)235.7 V7.08 V (2.95%)1716.5 WDrop/Amp High
350 kcmil177.3 mm²310 A3.68 V (1.53%)236.3 V6.07 V (2.53%)1471.6 WDrop/Amp High
400 kcmil202.7 mm²335 A3.22 V (1.34%)236.8 V5.31 V (2.21%)1287.2 WDrop/Amp High
500 kcmil253.4 mm²380 A2.57 V (1.07%)237.4 V4.25 V (1.77%)1029.6 WDrop/Amp High
600 kcmil304.0 mm²420 A2.15 V (0.89%)237.9 V3.54 V (1.47%)858.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.72 V (0.72%)238.3 V2.83 V (1.18%)686.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.29 V (0.54%)238.7 V2.12 V (0.88%)514.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 125 feet one-way at 240V (1-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 2.15V (0.89%) and delivers 237.9V at the load.

What size aluminum wire is required for 400 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.12V (0.88%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.