50 Amp Wire Size at 125 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 50 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.76%
Aluminum Wire (≤3% Drop)6 AWGDrop: 8.76V (1.82%)
Voltage at Load End471.6 VLoss: 8.44 V (730.6 W)
Power & Breaker (125%)41.57 kW63A Breaker Recommended

All AWG & kcmil Wire Gauges for 50 Amps at 125 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A33.95 V (7.07%)446.1 V56.0 V (11.67%)2939.9 WDrop/Amp High
12 AWG3.31 mm²20 A21.33 V (4.44%)458.7 V35.19 V (7.33%)1847.4 WDrop/Amp High
10 AWG5.26 mm²30 A13.42 V (2.8%)466.6 V22.14 V (4.61%)1162.6 WDrop/Amp High
8 AWG8.37 mm²50 A8.44 V (1.76%)471.6 V13.92 V (2.9%)730.6 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A5.31 V (1.11%)474.7 V8.76 V (1.82%)459.8 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A3.34 V (0.7%)476.7 V5.51 V (1.15%)289.1 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.65 V (0.55%)477.4 V4.37 V (0.91%)229.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.1 V (0.44%)477.9 V3.46 V (0.72%)181.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.66 V (0.35%)478.3 V2.75 V (0.57%)144.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.32 V (0.28%)478.7 V2.18 V (0.45%)114.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.05 V (0.22%)479.0 V1.73 V (0.36%)90.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.83 V (0.17%)479.2 V1.37 V (0.29%)71.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.66 V (0.14%)479.3 V1.09 V (0.23%)57.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.56 V (0.12%)479.4 V0.92 V (0.19%)48.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.46 V (0.1%)479.5 V0.77 V (0.16%)40.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.4 V (0.08%)479.6 V0.66 V (0.14%)34.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.35 V (0.07%)479.7 V0.57 V (0.12%)30.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.28 V (0.06%)479.7 V0.46 V (0.1%)24.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.23 V (0.05%)479.8 V0.38 V (0.08%)20.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.19 V (0.04%)479.8 V0.31 V (0.06%)16.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (0.03%)479.9 V0.23 V (0.05%)12.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 50 amps at 125 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 50A load over 125 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 8.44V (1.76%) and delivers 471.6V at the load.

What size aluminum wire is required for 50 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 8.76V (1.82%).

What breaker size is needed for a 50A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (50A × 1.25 = 62.5A), which corresponds to a standard 63A circuit breaker.