⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 125 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 0.87%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 4.32V (0.9%)
Voltage at Load End475.8 VLoss: 4.16 V (901.2 W)
Power & Breaker (125%)103.92 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 125 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A84.87 V (17.68%)395.1 V139.99 V (29.17%)18374.5 WDrop/Amp High
12 AWG3.31 mm²20 A53.33 V (11.11%)426.7 V87.97 V (18.33%)11546.5 WDrop/Amp High
10 AWG5.26 mm²30 A33.56 V (6.99%)446.4 V55.36 V (11.53%)7266.0 WDrop/Amp High
8 AWG8.37 mm²50 A21.09 V (4.39%)458.9 V34.79 V (7.25%)4566.2 WDrop/Amp High
6 AWG13.3 mm²65 A13.27 V (2.77%)466.7 V21.89 V (4.56%)2873.6 WDrop/Amp High
4 AWG21.15 mm²85 A8.35 V (1.74%)471.7 V13.77 V (2.87%)1807.0 WDrop/Amp High
3 AWG26.67 mm²100 A6.62 V (1.38%)473.4 V10.92 V (2.27%)1433.0 WDrop/Amp High
2 AWG33.62 mm²115 A5.25 V (1.09%)474.7 V8.66 V (1.8%)1136.8 WDrop/Amp High
1 AWG42.41 mm²130 A4.16 V (0.87%)475.8 V6.87 V (1.43%)901.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A3.3 V (0.69%)476.7 V5.44 V (1.13%)714.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.62 V (0.55%)477.4 V4.32 V (0.9%)566.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.08 V (0.43%)477.9 V3.43 V (0.71%)449.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.65 V (0.34%)478.4 V2.72 V (0.57%)356.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.39 V (0.29%)478.6 V2.3 V (0.48%)301.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.16 V (0.24%)478.8 V1.92 V (0.4%)251.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.0 V (0.21%)479.0 V1.64 V (0.34%)215.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.87 V (0.18%)479.1 V1.44 V (0.3%)188.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.7 V (0.15%)479.3 V1.15 V (0.24%)150.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.58 V (0.12%)479.4 V0.96 V (0.2%)125.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.46 V (0.1%)479.5 V0.77 V (0.16%)100.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.35 V (0.07%)479.7 V0.57 V (0.12%)75.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 125 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 125 feet one-way at 480V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 4.16V (0.87%) and delivers 475.8V at the load.

What size aluminum wire is required for 125 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 4.32V (0.9%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.