🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 125 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.01%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.8V (6.64%)
Voltage at Load End11.8 VLoss: 0.24 V (36.2 W)
Power & Breaker (125%)1.8 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 125 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A117.6 V (979.98%)0.0 V193.98 V (1616.5%)17639.6 WDrop/Amp High
12 AWG3.31 mm²20 A73.9 V (615.82%)0.0 V121.9 V (1015.81%)11084.7 WDrop/Amp High
10 AWG5.26 mm²30 A46.5 V (387.52%)0.0 V76.71 V (639.23%)6975.3 WDrop/Amp High
8 AWG8.37 mm²50 A29.22 V (243.53%)0.0 V48.21 V (401.71%)4383.5 WDrop/Amp High
6 AWG13.3 mm²65 A18.39 V (153.26%)0.0 V30.34 V (252.81%)2758.7 WDrop/Amp High
4 AWG21.15 mm²85 A11.57 V (96.38%)0.4 V19.08 V (158.98%)1734.8 WDrop/Amp High
3 AWG26.67 mm²100 A9.17 V (76.43%)2.8 V15.13 V (126.07%)1375.7 WDrop/Amp High
2 AWG33.62 mm²115 A7.28 V (60.63%)4.7 V12.0 V (100.01%)1091.3 WDrop/Amp High
1 AWG42.41 mm²130 A5.77 V (48.06%)6.2 V9.51 V (79.28%)865.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.57 V (38.11%)7.4 V7.54 V (62.86%)685.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.63 V (30.23%)8.4 V5.98 V (49.86%)544.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.88 V (23.98%)9.1 V4.75 V (39.55%)431.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.28 V (19.01%)9.7 V3.76 V (31.36%)342.3 WDrop/Amp High
250 kcmil126.7 mm²255 A1.93 V (16.09%)10.1 V3.18 V (26.54%)289.6 WDrop/Amp High
300 kcmil152.0 mm²285 A1.61 V (13.41%)10.4 V2.65 V (22.12%)241.4 WDrop/Amp High
350 kcmil177.3 mm²310 A1.38 V (11.5%)10.6 V2.28 V (18.96%)206.9 WDrop/Amp High
400 kcmil202.7 mm²335 A1.21 V (10.06%)10.8 V1.99 V (16.59%)181.0 WDrop/Amp High
500 kcmil253.4 mm²380 A0.97 V (8.04%)11.0 V1.59 V (13.27%)144.8 WDrop/Amp High
600 kcmil304.0 mm²420 A0.8 V (6.71%)11.2 V1.33 V (11.06%)120.7 WDrop/Amp High
750 kcmil380.0 mm²475 A0.64 V (5.36%)11.4 V1.06 V (8.85%)96.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.48 V (4.02%)11.5 V0.8 V (6.64%)72.4 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 125 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 125 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.24V (2.01%) and delivers 11.8V at the load.

What size aluminum wire is required for 150 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.8V (6.64%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.