🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 20 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.57%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 0.32V (2.65%)
Voltage at Load End11.7 VLoss: 0.31 V (46.3 W)
Power & Breaker (125%)1.8 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 20 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A18.82 V (156.8%)0.0 V31.04 V (258.64%)2822.3 WDrop/Amp High
12 AWG3.31 mm²20 A11.82 V (98.53%)0.2 V19.5 V (162.53%)1773.5 WDrop/Amp High
10 AWG5.26 mm²30 A7.44 V (62.0%)4.6 V12.27 V (102.28%)1116.1 WDrop/Amp High
8 AWG8.37 mm²50 A4.68 V (38.96%)7.3 V7.71 V (64.27%)701.4 WDrop/Amp High
6 AWG13.3 mm²65 A2.94 V (24.52%)9.1 V4.85 V (40.45%)441.4 WDrop/Amp High
4 AWG21.15 mm²85 A1.85 V (15.42%)10.1 V3.05 V (25.44%)277.6 WDrop/Amp High
3 AWG26.67 mm²100 A1.47 V (12.23%)10.5 V2.42 V (20.17%)220.1 WDrop/Amp High
2 AWG33.62 mm²115 A1.16 V (9.7%)10.8 V1.92 V (16.0%)174.6 WDrop/Amp High
1 AWG42.41 mm²130 A0.92 V (7.69%)11.1 V1.52 V (12.69%)138.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A0.73 V (6.1%)11.3 V1.21 V (10.06%)109.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A0.58 V (4.84%)11.4 V0.96 V (7.98%)87.1 W~ ≤5%
3/0 AWG85.01 mm²200 A0.46 V (3.84%)11.5 V0.76 V (6.33%)69.1 W~ ≤5%
4/0 AWG107.2 mm²230 A0.37 V (3.04%)11.6 V0.6 V (5.02%)54.8 W~ ≤5%
250 kcmil126.7 mm²255 A0.31 V (2.57%)11.7 V0.51 V (4.25%)46.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.26 V (2.15%)11.7 V0.42 V (3.54%)38.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.22 V (1.84%)11.8 V0.36 V (3.03%)33.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.19 V (1.61%)11.8 V0.32 V (2.65%)29.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.15 V (1.29%)11.8 V0.25 V (2.12%)23.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.13 V (1.07%)11.9 V0.21 V (1.77%)19.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.1 V (0.86%)11.9 V0.17 V (1.42%)15.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.64%)11.9 V0.13 V (1.06%)11.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 20 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 20 feet one-way at 12V (DC), you need 250 kcmil copper wire. This produces a voltage drop of 0.31V (2.57%) and delivers 11.7V at the load.

What size aluminum wire is required for 150 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 0.32V (2.65%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.