⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 125 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 1.53%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 3.8V (1.58%)
Voltage at Load End236.3 VLoss: 3.67 V (1110.9 W)
Power & Breaker (125%)72.75 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A118.82 V (49.51%)121.2 V195.99 V (81.66%)36014.1 WDrop/Amp High
12 AWG3.31 mm²20 A74.66 V (31.11%)165.3 V123.16 V (51.32%)22631.2 WDrop/Amp High
10 AWG5.26 mm²30 A46.98 V (19.58%)193.0 V77.5 V (32.29%)14241.3 WDrop/Amp High
8 AWG8.37 mm²50 A29.53 V (12.3%)210.5 V48.7 V (20.29%)8949.7 WDrop/Amp High
6 AWG13.3 mm²65 A18.58 V (7.74%)221.4 V30.65 V (12.77%)5632.3 WDrop/Amp High
4 AWG21.15 mm²85 A11.68 V (4.87%)228.3 V19.27 V (8.03%)3541.8 WDrop/Amp High
3 AWG26.67 mm²100 A9.27 V (3.86%)230.7 V15.29 V (6.37%)2808.7 WDrop/Amp High
2 AWG33.62 mm²115 A7.35 V (3.06%)232.6 V12.13 V (5.05%)2228.1 WDrop/Amp High
1 AWG42.41 mm²130 A5.83 V (2.43%)234.2 V9.61 V (4.01%)1766.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.62 V (1.93%)235.4 V7.62 V (3.18%)1400.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.67 V (1.53%)236.3 V6.05 V (2.52%)1110.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.91 V (1.21%)237.1 V4.8 V (2.0%)881.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.31 V (0.96%)237.7 V3.8 V (1.58%)698.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.95 V (0.81%)238.0 V3.22 V (1.34%)591.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.63 V (0.68%)238.4 V2.68 V (1.12%)492.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.39 V (0.58%)238.6 V2.3 V (0.96%)422.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.22 V (0.51%)238.8 V2.01 V (0.84%)369.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.98 V (0.41%)239.0 V1.61 V (0.67%)295.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.81 V (0.34%)239.2 V1.34 V (0.56%)246.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.65 V (0.27%)239.3 V1.07 V (0.45%)197.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.49 V (0.2%)239.5 V0.8 V (0.34%)147.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 125 feet one-way at 240V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 3.67V (1.53%) and delivers 236.3V at the load.

What size aluminum wire is required for 175 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 3.8V (1.58%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.