⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 60 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 0.73%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 1.83V (0.76%)
Voltage at Load End238.2 VLoss: 1.76 V (533.2 W)
Power & Breaker (125%)72.75 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 60 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A57.03 V (23.76%)183.0 V94.08 V (39.2%)17286.8 WDrop/Amp High
12 AWG3.31 mm²20 A35.84 V (14.93%)204.2 V59.12 V (24.63%)10863.0 WDrop/Amp High
10 AWG5.26 mm²30 A22.55 V (9.4%)217.4 V37.2 V (15.5%)6835.8 WDrop/Amp High
8 AWG8.37 mm²50 A14.17 V (5.91%)225.8 V23.38 V (9.74%)4295.9 WDrop/Amp High
6 AWG13.3 mm²65 A8.92 V (3.72%)231.1 V14.71 V (6.13%)2703.5 WDrop/Amp High
4 AWG21.15 mm²85 A5.61 V (2.34%)234.4 V9.25 V (3.85%)1700.1 WDrop/Amp High
3 AWG26.67 mm²100 A4.45 V (1.85%)235.6 V7.34 V (3.06%)1348.2 WDrop/Amp High
2 AWG33.62 mm²115 A3.53 V (1.47%)236.5 V5.82 V (2.43%)1069.5 WDrop/Amp High
1 AWG42.41 mm²130 A2.8 V (1.17%)237.2 V4.61 V (1.92%)847.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.22 V (0.92%)237.8 V3.66 V (1.52%)672.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.76 V (0.73%)238.2 V2.9 V (1.21%)533.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.4 V (0.58%)238.6 V2.3 V (0.96%)423.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.11 V (0.46%)238.9 V1.83 V (0.76%)335.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.94 V (0.39%)239.1 V1.54 V (0.64%)283.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.78 V (0.33%)239.2 V1.29 V (0.54%)236.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.67 V (0.28%)239.3 V1.1 V (0.46%)202.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.59 V (0.24%)239.4 V0.97 V (0.4%)177.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.47 V (0.2%)239.5 V0.77 V (0.32%)141.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.39 V (0.16%)239.6 V0.64 V (0.27%)118.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.31 V (0.13%)239.7 V0.51 V (0.21%)94.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.23 V (0.1%)239.8 V0.39 V (0.16%)71.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 60 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 60 feet one-way at 240V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 1.76V (0.73%) and delivers 238.2V at the load.

What size aluminum wire is required for 175 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 1.83V (0.76%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.