🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 50 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 0.61%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 1.52V (0.63%)
Voltage at Load End238.5 VLoss: 1.47 V (444.4 W)
Power & Breaker (125%)72.75 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 50 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A47.53 V (19.8%)192.5 V78.4 V (32.67%)14405.6 WDrop/Amp High
12 AWG3.31 mm²20 A29.87 V (12.44%)210.1 V49.26 V (20.53%)9052.5 WDrop/Amp High
10 AWG5.26 mm²30 A18.79 V (7.83%)221.2 V31.0 V (12.92%)5696.5 WDrop/Amp High
8 AWG8.37 mm²50 A11.81 V (4.92%)228.2 V19.48 V (8.12%)3579.9 WDrop/Amp High
6 AWG13.3 mm²65 A7.43 V (3.1%)232.6 V12.26 V (5.11%)2252.9 WDrop/Amp High
4 AWG21.15 mm²85 A4.67 V (1.95%)235.3 V7.71 V (3.21%)1416.7 WDrop/Amp High
3 AWG26.67 mm²100 A3.71 V (1.54%)236.3 V6.11 V (2.55%)1123.5 WDrop/Amp High
2 AWG33.62 mm²115 A2.94 V (1.23%)237.1 V4.85 V (2.02%)891.2 WDrop/Amp High
1 AWG42.41 mm²130 A2.33 V (0.97%)237.7 V3.84 V (1.6%)706.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.85 V (0.77%)238.2 V3.05 V (1.27%)560.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.47 V (0.61%)238.5 V2.42 V (1.01%)444.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.16 V (0.48%)238.8 V1.92 V (0.8%)352.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.92 V (0.38%)239.1 V1.52 V (0.63%)279.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.78 V (0.33%)239.2 V1.29 V (0.54%)236.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.65 V (0.27%)239.3 V1.07 V (0.45%)197.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.56 V (0.23%)239.4 V0.92 V (0.38%)169.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.49 V (0.2%)239.5 V0.8 V (0.34%)147.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.39 V (0.16%)239.6 V0.64 V (0.27%)118.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.33 V (0.14%)239.7 V0.54 V (0.22%)98.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.26 V (0.11%)239.7 V0.43 V (0.18%)78.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.2 V (0.08%)239.8 V0.32 V (0.13%)59.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 50 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 50 feet one-way at 240V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 1.47V (0.61%) and delivers 238.5V at the load.

What size aluminum wire is required for 175 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 1.52V (0.63%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.