🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 30 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 0.37%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 0.91V (0.38%)
Voltage at Load End239.1 VLoss: 0.88 V (266.6 W)
Power & Breaker (125%)72.75 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A28.52 V (11.88%)211.5 V47.04 V (19.6%)8643.4 WDrop/Amp High
12 AWG3.31 mm²20 A17.92 V (7.47%)222.1 V29.56 V (12.32%)5431.5 WDrop/Amp High
10 AWG5.26 mm²30 A11.28 V (4.7%)228.7 V18.6 V (7.75%)3417.9 WDrop/Amp High
8 AWG8.37 mm²50 A7.09 V (2.95%)232.9 V11.69 V (4.87%)2147.9 WDrop/Amp High
6 AWG13.3 mm²65 A4.46 V (1.86%)235.5 V7.36 V (3.07%)1351.7 WDrop/Amp High
4 AWG21.15 mm²85 A2.8 V (1.17%)237.2 V4.63 V (1.93%)850.0 WDrop/Amp High
3 AWG26.67 mm²100 A2.22 V (0.93%)237.8 V3.67 V (1.53%)674.1 WDrop/Amp High
2 AWG33.62 mm²115 A1.76 V (0.74%)238.2 V2.91 V (1.21%)534.7 WDrop/Amp High
1 AWG42.41 mm²130 A1.4 V (0.58%)238.6 V2.31 V (0.96%)423.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.11 V (0.46%)238.9 V1.83 V (0.76%)336.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A0.88 V (0.37%)239.1 V1.45 V (0.6%)266.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.7 V (0.29%)239.3 V1.15 V (0.48%)211.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.55 V (0.23%)239.4 V0.91 V (0.38%)167.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.47 V (0.2%)239.5 V0.77 V (0.32%)141.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.39 V (0.16%)239.6 V0.64 V (0.27%)118.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.33 V (0.14%)239.7 V0.55 V (0.23%)101.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.29 V (0.12%)239.7 V0.48 V (0.2%)88.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.23 V (0.1%)239.8 V0.39 V (0.16%)70.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.2 V (0.08%)239.8 V0.32 V (0.13%)59.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.16 V (0.07%)239.8 V0.26 V (0.11%)47.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.12 V (0.05%)239.9 V0.19 V (0.08%)35.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 30 feet one-way at 240V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 0.88V (0.37%) and delivers 239.1V at the load.

What size aluminum wire is required for 175 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 0.91V (0.38%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.