🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 275 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.58%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.04V (17.03%)
Voltage at Load End11.7 VLoss: 0.31 V (54.2 W)
Power & Breaker (125%)2.1 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 275 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A301.83 V (2515.27%)0.0 V497.88 V (4149.02%)52820.7 WDrop/Amp High
12 AWG3.31 mm²20 A189.67 V (1580.59%)0.0 V312.87 V (2607.24%)33192.5 WDrop/Amp High
10 AWG5.26 mm²30 A119.36 V (994.63%)0.0 V196.88 V (1640.68%)20887.3 WDrop/Amp High
8 AWG8.37 mm²50 A75.01 V (625.06%)0.0 V123.73 V (1031.06%)13126.3 WDrop/Amp High
6 AWG13.3 mm²65 A47.2 V (393.37%)0.0 V77.86 V (648.87%)8260.7 WDrop/Amp High
4 AWG21.15 mm²85 A29.68 V (247.36%)0.0 V48.96 V (408.04%)5194.7 WDrop/Amp High
3 AWG26.67 mm²100 A23.54 V (196.17%)0.0 V38.83 V (323.58%)4119.5 WDrop/Amp High
2 AWG33.62 mm²115 A18.67 V (155.61%)0.0 V30.8 V (256.69%)3267.9 WDrop/Amp High
1 AWG42.41 mm²130 A14.8 V (123.36%)0.0 V24.42 V (203.49%)2590.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.74 V (97.81%)0.3 V19.36 V (161.34%)2054.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.31 V (77.59%)2.7 V15.36 V (127.98%)1629.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.39 V (61.54%)4.6 V12.18 V (101.52%)1292.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.86 V (48.8%)6.1 V9.66 V (80.5%)1024.9 WDrop/Amp High
250 kcmil126.7 mm²255 A4.96 V (41.29%)7.0 V8.17 V (68.11%)867.1 WDrop/Amp High
300 kcmil152.0 mm²285 A4.13 V (34.42%)7.9 V6.81 V (56.78%)722.8 WDrop/Amp High
350 kcmil177.3 mm²310 A3.54 V (29.51%)8.5 V5.84 V (48.67%)619.7 WDrop/Amp High
400 kcmil202.7 mm²335 A3.1 V (25.81%)8.9 V5.11 V (42.58%)542.0 WDrop/Amp High
500 kcmil253.4 mm²380 A2.48 V (20.65%)9.5 V4.09 V (34.06%)433.6 WDrop/Amp High
600 kcmil304.0 mm²420 A2.07 V (17.21%)9.9 V3.41 V (28.39%)361.4 WDrop/Amp High
750 kcmil380.0 mm²475 A1.65 V (13.77%)10.3 V2.73 V (22.71%)289.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.24 V (10.33%)10.8 V2.04 V (17.03%)216.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 275 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 275 feet one-way at 12V (DC), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.31V (2.58%) and delivers 11.7V at the load.

What size aluminum wire is required for 175 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.04V (17.03%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.