🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 350 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.63%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.6V (21.68%)
Voltage at Load End11.7 VLoss: 0.32 V (55.2 W)
Power & Breaker (125%)2.1 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 350 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A384.15 V (3201.25%)0.0 V633.67 V (5280.57%)67226.4 WDrop/Amp High
12 AWG3.31 mm²20 A241.4 V (2011.66%)0.0 V398.2 V (3318.31%)42245.0 WDrop/Amp High
10 AWG5.26 mm²30 A151.91 V (1265.9%)0.0 V250.58 V (2088.14%)26583.8 WDrop/Amp High
8 AWG8.37 mm²50 A95.46 V (795.53%)0.0 V157.47 V (1312.26%)16706.2 WDrop/Amp High
6 AWG13.3 mm²65 A60.08 V (500.65%)0.0 V99.1 V (825.83%)10513.6 WDrop/Amp High
4 AWG21.15 mm²85 A37.78 V (314.83%)0.0 V62.32 V (519.32%)6611.4 WDrop/Amp High
3 AWG26.67 mm²100 A29.96 V (249.67%)0.0 V49.42 V (411.83%)5243.0 WDrop/Amp High
2 AWG33.62 mm²115 A23.77 V (198.06%)0.0 V39.2 V (326.7%)4159.2 WDrop/Amp High
1 AWG42.41 mm²130 A18.84 V (157.01%)0.0 V31.08 V (258.99%)3297.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A14.94 V (124.48%)0.0 V24.64 V (205.34%)2614.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.85 V (98.75%)0.2 V19.55 V (162.89%)2073.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.4 V (78.33%)2.6 V15.5 V (129.2%)1644.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.45 V (62.11%)4.5 V12.3 V (102.46%)1304.4 WDrop/Amp High
250 kcmil126.7 mm²255 A6.31 V (52.55%)5.7 V10.4 V (86.69%)1103.6 WDrop/Amp High
300 kcmil152.0 mm²285 A5.26 V (43.81%)6.7 V8.67 V (72.26%)919.9 WDrop/Amp High
350 kcmil177.3 mm²310 A4.51 V (37.56%)7.5 V7.43 V (61.95%)788.7 WDrop/Amp High
400 kcmil202.7 mm²335 A3.94 V (32.85%)8.1 V6.5 V (54.19%)689.8 WDrop/Amp High
500 kcmil253.4 mm²380 A3.15 V (26.28%)8.8 V5.2 V (43.34%)551.8 WDrop/Amp High
600 kcmil304.0 mm²420 A2.63 V (21.9%)9.4 V4.34 V (36.13%)460.0 WDrop/Amp High
750 kcmil380.0 mm²475 A2.1 V (17.52%)9.9 V3.47 V (28.9%)368.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.58 V (13.14%)10.4 V2.6 V (21.68%)276.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 350 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 350 feet one-way at 12V (DC), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.32V (2.63%) and delivers 11.7V at the load.

What size aluminum wire is required for 175 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.6V (21.68%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.