🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 400 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)6× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.5%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.97V (24.77%)
Voltage at Load End11.7 VLoss: 0.3 V (52.6 W)
Power & Breaker (125%)2.1 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 400 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A439.03 V (3658.58%)0.0 V724.19 V (6034.94%)76830.1 WDrop/Amp High
12 AWG3.31 mm²20 A275.89 V (2299.05%)0.0 V455.08 V (3792.35%)48280.0 WDrop/Amp High
10 AWG5.26 mm²30 A173.61 V (1446.74%)0.0 V286.37 V (2386.44%)30381.5 WDrop/Amp High
8 AWG8.37 mm²50 A109.1 V (909.18%)0.0 V179.97 V (1499.72%)19092.8 WDrop/Amp High
6 AWG13.3 mm²65 A68.66 V (572.17%)0.0 V113.26 V (943.81%)12015.5 WDrop/Amp High
4 AWG21.15 mm²85 A43.18 V (359.8%)0.0 V71.22 V (593.51%)7555.9 WDrop/Amp High
3 AWG26.67 mm²100 A34.24 V (285.33%)0.0 V56.48 V (470.67%)5992.0 WDrop/Amp High
2 AWG33.62 mm²115 A27.16 V (226.35%)0.0 V44.8 V (373.37%)4753.3 WDrop/Amp High
1 AWG42.41 mm²130 A21.53 V (179.44%)0.0 V35.52 V (295.98%)3768.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.07 V (142.27%)0.0 V28.16 V (234.67%)2987.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.54 V (112.86%)0.0 V22.34 V (186.16%)2370.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.74 V (89.52%)1.3 V17.72 V (147.66%)1879.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.52 V (70.99%)3.5 V14.05 V (117.1%)1490.7 WDrop/Amp High
250 kcmil126.7 mm²255 A7.21 V (60.06%)4.8 V11.89 V (99.07%)1261.3 WDrop/Amp High
300 kcmil152.0 mm²285 A6.01 V (50.06%)6.0 V9.91 V (82.58%)1051.4 WDrop/Amp High
350 kcmil177.3 mm²310 A5.15 V (42.92%)6.8 V8.5 V (70.8%)901.3 WDrop/Amp High
400 kcmil202.7 mm²335 A4.51 V (37.54%)7.5 V7.43 V (61.93%)788.4 WDrop/Amp High
500 kcmil253.4 mm²380 A3.6 V (30.03%)8.4 V5.94 V (49.54%)630.6 WDrop/Amp High
600 kcmil304.0 mm²420 A3.0 V (25.03%)9.0 V4.96 V (41.29%)525.7 WDrop/Amp High
750 kcmil380.0 mm²475 A2.4 V (20.03%)9.6 V3.96 V (33.03%)420.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.8 V (15.02%)10.2 V2.97 V (24.77%)315.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 400 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 400 feet one-way at 12V (DC), you need 6× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.3V (2.5%) and delivers 11.7V at the load.

What size aluminum wire is required for 175 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.97V (24.77%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.