🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 600 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 5.95V (2.48%)
Voltage at Load End233.2 VLoss: 6.76 V (1182.6 W)
Power & Breaker (125%)42.0 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A658.54 V (274.39%)0.0 V1086.29 V (452.62%)115245.2 WDrop/Amp High
12 AWG3.31 mm²20 A413.83 V (172.43%)0.0 V682.62 V (284.43%)72419.9 WDrop/Amp High
10 AWG5.26 mm²30 A260.41 V (108.51%)0.0 V429.56 V (178.98%)45572.2 WDrop/Amp High
8 AWG8.37 mm²50 A163.65 V (68.19%)76.3 V269.95 V (112.48%)28639.2 WDrop/Amp High
6 AWG13.3 mm²65 A102.99 V (42.91%)137.0 V169.89 V (70.79%)18023.3 WDrop/Amp High
4 AWG21.15 mm²85 A64.76 V (26.99%)175.2 V106.83 V (44.51%)11333.8 WDrop/Amp High
3 AWG26.67 mm²100 A51.36 V (21.4%)188.6 V84.72 V (35.3%)8988.0 WDrop/Amp High
2 AWG33.62 mm²115 A40.74 V (16.98%)199.3 V67.21 V (28.0%)7130.0 WDrop/Amp High
1 AWG42.41 mm²130 A32.3 V (13.46%)207.7 V53.28 V (22.2%)5652.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.61 V (10.67%)214.4 V42.24 V (17.6%)4481.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.31 V (8.46%)219.7 V33.51 V (13.96%)3554.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.11 V (6.71%)223.9 V26.58 V (11.07%)2819.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.78 V (5.32%)227.2 V21.08 V (8.78%)2236.1 WDrop/Amp High
250 kcmil126.7 mm²255 A10.81 V (4.5%)229.2 V17.83 V (7.43%)1891.9 W~ ≤5%
300 kcmil152.0 mm²285 A9.01 V (3.75%)231.0 V14.87 V (6.19%)1577.0 W~ ≤5%
350 kcmil177.3 mm²310 A7.73 V (3.22%)232.3 V12.74 V (5.31%)1352.0 W~ ≤5%
400 kcmil202.7 mm²335 A6.76 V (2.82%)233.2 V11.15 V (4.64%)1182.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A5.41 V (2.25%)234.6 V8.92 V (3.72%)946.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.51 V (1.88%)235.5 V7.43 V (3.1%)788.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.6 V (1.5%)236.4 V5.95 V (2.48%)630.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.7 V (1.13%)237.3 V4.46 V (1.86%)473.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 600 feet one-way at 240V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 6.76V (2.82%) and delivers 233.2V at the load.

What size aluminum wire is required for 175 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 5.95V (2.48%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.