🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 750 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.57V (4.65%)
Voltage at Load End116.6 VLoss: 3.38 V (591.4 W)
Power & Breaker (125%)21.0 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 750 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A823.18 V (685.98%)0.0 V1357.86 V (1131.55%)144056.5 WDrop/Amp High
12 AWG3.31 mm²20 A517.29 V (431.07%)0.0 V853.28 V (711.07%)90524.9 WDrop/Amp High
10 AWG5.26 mm²30 A325.52 V (271.26%)0.0 V536.95 V (447.46%)56965.3 WDrop/Amp High
8 AWG8.37 mm²50 A204.57 V (170.47%)0.0 V337.44 V (281.2%)35799.0 WDrop/Amp High
6 AWG13.3 mm²65 A128.74 V (107.28%)0.0 V212.36 V (176.96%)22529.1 WDrop/Amp High
4 AWG21.15 mm²85 A80.96 V (67.46%)39.0 V133.54 V (111.28%)14167.3 WDrop/Amp High
3 AWG26.67 mm²100 A64.2 V (53.5%)55.8 V105.9 V (88.25%)11235.0 WDrop/Amp High
2 AWG33.62 mm²115 A50.93 V (42.44%)69.1 V84.01 V (70.01%)8912.5 WDrop/Amp High
1 AWG42.41 mm²130 A40.37 V (33.64%)79.6 V66.6 V (55.5%)7065.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A32.01 V (26.67%)88.0 V52.8 V (44.0%)5601.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A25.39 V (21.16%)94.6 V41.89 V (34.9%)4443.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A20.14 V (16.78%)99.9 V33.22 V (27.69%)3524.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.97 V (13.31%)104.0 V26.35 V (21.96%)2795.1 WDrop/Amp High
250 kcmil126.7 mm²255 A13.51 V (11.26%)106.5 V22.29 V (18.58%)2364.9 WDrop/Amp High
300 kcmil152.0 mm²285 A11.26 V (9.39%)108.7 V18.58 V (15.48%)1971.3 WDrop/Amp High
350 kcmil177.3 mm²310 A9.66 V (8.05%)110.3 V15.93 V (13.27%)1690.0 WDrop/Amp High
400 kcmil202.7 mm²335 A8.45 V (7.04%)111.6 V13.93 V (11.61%)1478.2 WDrop/Amp High
500 kcmil253.4 mm²380 A6.76 V (5.63%)113.2 V11.15 V (9.29%)1182.5 WDrop/Amp High
600 kcmil304.0 mm²420 A5.63 V (4.69%)114.4 V9.29 V (7.74%)985.6 W~ ≤5%
750 kcmil380.0 mm²475 A4.51 V (3.75%)115.5 V7.43 V (6.19%)788.5 W~ ≤5%
1000 kcmil506.7 mm²545 A3.38 V (2.82%)116.6 V5.57 V (4.65%)591.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 750 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 750 feet one-way at 120V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 3.38V (2.82%) and delivers 116.6V at the load.

What size aluminum wire is required for 175 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.57V (4.65%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.