🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

20 Amp Wire Size at 350 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 20 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.85%
Aluminum Wire (≤3% Drop)1 AWGDrop: 3.55V (2.96%)
Voltage at Load End116.6 VLoss: 3.42 V (68.5 W)
Power & Breaker (125%)2.4 kW25A Breaker Recommended

All AWG & kcmil Wire Gauges for 20 Amps at 350 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A43.9 V (36.59%)76.1 V72.42 V (60.35%)878.1 WDrop/Amp High
12 AWG3.31 mm²20 A27.59 V (22.99%)92.4 V45.51 V (37.92%)551.8 WDrop/Amp High
10 AWG5.26 mm²30 A17.36 V (14.47%)102.6 V28.64 V (23.86%)347.2 WDrop/Amp High
8 AWG8.37 mm²50 A10.91 V (9.09%)109.1 V18.0 V (15.0%)218.2 WDrop/Amp High
6 AWG13.3 mm²65 A6.87 V (5.72%)113.1 V11.33 V (9.44%)137.3 WDrop/Amp High
4 AWG21.15 mm²85 A4.32 V (3.6%)115.7 V7.12 V (5.94%)86.4 W~ ≤5%
3 AWG26.67 mm²100 A3.42 V (2.85%)116.6 V5.65 V (4.71%)68.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.72 V (2.26%)117.3 V4.48 V (3.73%)54.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.15 V (1.79%)117.8 V3.55 V (2.96%)43.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.71 V (1.42%)118.3 V2.82 V (2.35%)34.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.35 V (1.13%)118.6 V2.23 V (1.86%)27.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.07 V (0.9%)118.9 V1.77 V (1.48%)21.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.85 V (0.71%)119.1 V1.41 V (1.17%)17.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.72 V (0.6%)119.3 V1.19 V (0.99%)14.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.6 V (0.5%)119.4 V0.99 V (0.83%)12.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.52 V (0.43%)119.5 V0.85 V (0.71%)10.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.45 V (0.38%)119.5 V0.74 V (0.62%)9.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.36 V (0.3%)119.6 V0.59 V (0.5%)7.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.3 V (0.25%)119.7 V0.5 V (0.41%)6.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.24 V (0.2%)119.8 V0.4 V (0.33%)4.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.18 V (0.15%)119.8 V0.3 V (0.25%)3.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 20 amps at 350 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 20A load over 350 feet one-way at 120V (1-Phase), you need 3 AWG copper wire. This produces a voltage drop of 3.42V (2.85%) and delivers 116.6V at the load.

What size aluminum wire is required for 20 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 3.55V (2.96%).

What breaker size is needed for a 20A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (20A × 1.25 = 25.0A), which corresponds to a standard 25A circuit breaker.