⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

200 Amp Wire Size at 200 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 200 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.86%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 3.4V (2.83%)
Voltage at Load End116.6 VLoss: 3.43 V (686.6 W)
Power & Breaker (125%)24.0 kW250A Breaker Recommended

All AWG & kcmil Wire Gauges for 200 Amps at 200 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A250.87 V (209.06%)0.0 V413.82 V (344.85%)50174.8 WDrop/Amp High
12 AWG3.31 mm²20 A157.65 V (131.37%)0.0 V260.05 V (216.71%)31529.8 WDrop/Amp High
10 AWG5.26 mm²30 A99.2 V (82.67%)20.8 V163.64 V (136.37%)19841.0 WDrop/Amp High
8 AWG8.37 mm²50 A62.34 V (51.95%)57.7 V102.84 V (85.7%)12468.8 WDrop/Amp High
6 AWG13.3 mm²65 A39.23 V (32.7%)80.8 V64.72 V (53.93%)7846.9 WDrop/Amp High
4 AWG21.15 mm²85 A24.67 V (20.56%)95.3 V40.7 V (33.91%)4934.4 WDrop/Amp High
3 AWG26.67 mm²100 A19.57 V (16.3%)100.4 V32.27 V (26.9%)3913.1 WDrop/Amp High
2 AWG33.62 mm²115 A15.52 V (12.93%)104.5 V25.6 V (21.34%)3104.2 WDrop/Amp High
1 AWG42.41 mm²130 A12.3 V (10.25%)107.7 V20.3 V (16.91%)2460.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.76 V (8.13%)110.2 V16.09 V (13.41%)1951.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.74 V (6.45%)112.3 V12.77 V (10.64%)1547.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.14 V (5.12%)113.9 V10.13 V (8.44%)1227.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.87 V (4.06%)115.1 V8.03 V (6.69%)973.5 W~ ≤5%
250 kcmil126.7 mm²255 A4.12 V (3.43%)115.9 V6.79 V (5.66%)823.7 W~ ≤5%
300 kcmil152.0 mm²285 A3.43 V (2.86%)116.6 V5.66 V (4.72%)686.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.94 V (2.45%)117.1 V4.85 V (4.05%)588.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.57 V (2.15%)117.4 V4.25 V (3.54%)514.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.06 V (1.72%)117.9 V3.4 V (2.83%)411.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.72 V (1.43%)118.3 V2.83 V (2.36%)343.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.37 V (1.14%)118.6 V2.27 V (1.89%)274.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.03 V (0.86%)119.0 V1.7 V (1.42%)206.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 200 amps at 200 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 200A load over 200 feet one-way at 120V (1-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 3.43V (2.86%) and delivers 116.6V at the load.

What size aluminum wire is required for 200 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 3.4V (2.83%).

What breaker size is needed for a 200A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (200A × 1.25 = 250.0A), which corresponds to a standard 250A circuit breaker.