200 Amp Wire Size at 600 Feet (480V Three-Phase (US Heavy Industrial))
Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 200 A load over a 600 ft (182.9 m) one-way run.
Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.63%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 12.61V (2.63%)
Voltage at Load End467.4 VLoss: 12.65 V (4380.9 W)
Power & Breaker (125%)166.28 kW250A Breaker Recommended
All AWG & kcmil Wire Gauges for 200 Amps at 600 Feet (480V)
| Wire Gauge | Metric Area | NEC 75°C Cu Ampacity | Copper Voltage Drop | Load Voltage | Aluminum Drop | Line Loss ($I^2R$) | NEC Status |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 mm² | 15 A | 651.79 V (135.79%) | 0.0 V | 1075.15 V (223.99%) | 225786.5 W | Drop/Amp High |
| 12 AWG | 3.31 mm² | 20 A | 409.58 V (85.33%) | 70.4 V | 675.62 V (140.75%) | 141883.9 W | Drop/Amp High |
| 10 AWG | 5.26 mm² | 30 A | 257.74 V (53.7%) | 222.3 V | 425.15 V (88.57%) | 89284.4 W | Drop/Amp High |
| 8 AWG | 8.37 mm² | 50 A | 161.97 V (33.74%) | 318.0 V | 267.18 V (55.66%) | 56109.4 W | Drop/Amp High |
| 6 AWG | 13.3 mm² | 65 A | 101.93 V (21.24%) | 378.1 V | 168.14 V (35.03%) | 35311.0 W | Drop/Amp High |
| 4 AWG | 21.15 mm² | 85 A | 64.1 V (13.35%) | 415.9 V | 105.74 V (22.03%) | 22205.0 W | Drop/Amp High |
| 3 AWG | 26.67 mm² | 100 A | 50.83 V (10.59%) | 429.2 V | 83.85 V (17.47%) | 17609.1 W | Drop/Amp High |
| 2 AWG | 33.62 mm² | 115 A | 40.32 V (8.4%) | 439.7 V | 66.52 V (13.86%) | 13968.9 W | Drop/Amp High |
| 1 AWG | 42.41 mm² | 130 A | 31.97 V (6.66%) | 448.0 V | 52.73 V (10.99%) | 11073.7 W | Drop/Amp High |
| 1/0 AWG | 53.49 mm² | 150 A | 25.35 V (5.28%) | 454.7 V | 41.81 V (8.71%) | 8779.9 W | Drop/Amp High |
| 2/0 AWG | 67.43 mm² | 175 A | 20.11 V (4.19%) | 459.9 V | 33.16 V (6.91%) | 6964.8 W | Drop/Amp High |
| 3/0 AWG | 85.01 mm² | 200 A | 15.95 V (3.32%) | 464.1 V | 26.31 V (5.48%) | 5524.5 W | ~ ≤5% |
| 4/0 AWG | 107.2 mm² | 230 A | 12.65 V (2.63%) | 467.4 V | 20.86 V (4.35%) | 4380.9 W | ✓ PASS (≤3%) |
| 250 kcmil | 126.7 mm² | 255 A | 10.7 V (2.23%) | 469.3 V | 17.65 V (3.68%) | 3706.7 W | ✓ PASS (≤3%) |
| 300 kcmil | 152.0 mm² | 285 A | 8.92 V (1.86%) | 471.1 V | 14.71 V (3.07%) | 3089.7 W | ✓ PASS (≤3%) |
| 350 kcmil | 177.3 mm² | 310 A | 7.65 V (1.59%) | 472.4 V | 12.61 V (2.63%) | 2648.8 W | ✓ PASS (≤3%) |
| 400 kcmil | 202.7 mm² | 335 A | 6.69 V (1.39%) | 473.3 V | 11.03 V (2.3%) | 2316.9 W | ✓ PASS (≤3%) |
| 500 kcmil | 253.4 mm² | 380 A | 5.35 V (1.11%) | 474.6 V | 8.83 V (1.84%) | 1853.3 W | ✓ PASS (≤3%) |
| 600 kcmil | 304.0 mm² | 420 A | 4.46 V (0.93%) | 475.5 V | 7.36 V (1.53%) | 1544.9 W | ✓ PASS (≤3%) |
| 750 kcmil | 380.0 mm² | 475 A | 3.57 V (0.74%) | 476.4 V | 5.89 V (1.23%) | 1235.9 W | ✓ PASS (≤3%) |
| 1000 kcmil | 506.7 mm² | 545 A | 2.68 V (0.56%) | 477.3 V | 4.41 V (0.92%) | 926.9 W | ✓ PASS (≤3%) |
Frequently Asked Engineering Questions
What size copper wire do I need for 200 amps at 600 feet (480V)?
To stay within the NEC recommended 3% maximum voltage drop for a 200A load over 600 feet one-way at 480V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 12.65V (2.63%) and delivers 467.4V at the load.
What size aluminum wire is required for 200 amps at 600 feet?
Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 12.61V (2.63%).
What breaker size is needed for a 200A continuous load?
Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (200A × 1.25 = 250.0A), which corresponds to a standard 250A circuit breaker.
Compare Other Distances & Amperages
200 Amp Wire Size by Distance (480V)
200A at 20 ft (480V)200A at 30 ft (480V)200A at 40 ft (480V)200A at 50 ft (480V)200A at 60 ft (480V)200A at 75 ft (480V)200A at 80 ft (480V)200A at 100 ft (480V)200A at 120 ft (480V)200A at 125 ft (480V)200A at 150 ft (480V)200A at 175 ft (480V)