🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 150 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 1.48%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 4.14V (1.72%)
Voltage at Load End236.4 VLoss: 3.56 V (1386.2 W)
Power & Breaker (125%)93.53 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A183.32 V (76.38%)56.7 V302.39 V (125.99%)71440.2 WDrop/Amp High
12 AWG3.31 mm²20 A115.2 V (48.0%)124.8 V190.02 V (79.17%)44893.0 WDrop/Amp High
10 AWG5.26 mm²30 A72.49 V (30.2%)167.5 V119.57 V (49.82%)28250.1 WDrop/Amp High
8 AWG8.37 mm²50 A45.56 V (18.98%)194.4 V75.14 V (31.31%)17753.4 WDrop/Amp High
6 AWG13.3 mm²65 A28.67 V (11.95%)211.3 V47.29 V (19.7%)11172.6 WDrop/Amp High
4 AWG21.15 mm²85 A18.03 V (7.51%)222.0 V29.74 V (12.39%)7025.8 WDrop/Amp High
3 AWG26.67 mm²100 A14.3 V (5.96%)225.7 V23.58 V (9.83%)5571.6 WDrop/Amp High
2 AWG33.62 mm²115 A11.34 V (4.73%)228.7 V18.71 V (7.79%)4419.9 WDrop/Amp High
1 AWG42.41 mm²130 A8.99 V (3.75%)231.0 V14.83 V (6.18%)3503.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.13 V (2.97%)232.9 V11.76 V (4.9%)2778.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.65 V (2.36%)234.3 V9.33 V (3.89%)2203.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.49 V (1.87%)235.5 V7.4 V (3.08%)1748.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.56 V (1.48%)236.4 V5.87 V (2.44%)1386.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.01 V (1.25%)237.0 V4.96 V (2.07%)1172.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.51 V (1.05%)237.5 V4.14 V (1.72%)977.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.15 V (0.9%)237.8 V3.55 V (1.48%)838.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.88 V (0.78%)238.1 V3.1 V (1.29%)733.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.5 V (0.63%)238.5 V2.48 V (1.03%)586.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.25 V (0.52%)238.7 V2.07 V (0.86%)488.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.0 V (0.42%)239.0 V1.66 V (0.69%)391.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.75 V (0.31%)239.2 V1.24 V (0.52%)293.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 150 feet one-way at 240V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 3.56V (1.48%) and delivers 236.4V at the load.

What size aluminum wire is required for 225 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 4.14V (1.72%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.