🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 30 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 0.3%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 0.83V (0.34%)
Voltage at Load End239.3 VLoss: 0.71 V (277.2 W)
Power & Breaker (125%)93.53 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A36.66 V (15.28%)203.3 V60.48 V (25.2%)14288.0 WDrop/Amp High
12 AWG3.31 mm²20 A23.04 V (9.6%)217.0 V38.0 V (15.83%)8978.6 WDrop/Amp High
10 AWG5.26 mm²30 A14.5 V (6.04%)225.5 V23.91 V (9.96%)5650.0 WDrop/Amp High
8 AWG8.37 mm²50 A9.11 V (3.8%)230.9 V15.03 V (6.26%)3550.7 WDrop/Amp High
6 AWG13.3 mm²65 A5.73 V (2.39%)234.3 V9.46 V (3.94%)2234.5 WDrop/Amp High
4 AWG21.15 mm²85 A3.61 V (1.5%)236.4 V5.95 V (2.48%)1405.2 WDrop/Amp High
3 AWG26.67 mm²100 A2.86 V (1.19%)237.1 V4.72 V (1.97%)1114.3 WDrop/Amp High
2 AWG33.62 mm²115 A2.27 V (0.95%)237.7 V3.74 V (1.56%)884.0 WDrop/Amp High
1 AWG42.41 mm²130 A1.8 V (0.75%)238.2 V2.97 V (1.24%)700.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.43 V (0.59%)238.6 V2.35 V (0.98%)555.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.13 V (0.47%)238.9 V1.87 V (0.78%)440.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.9 V (0.37%)239.1 V1.48 V (0.62%)349.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.71 V (0.3%)239.3 V1.17 V (0.49%)277.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.6 V (0.25%)239.4 V0.99 V (0.41%)234.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.5 V (0.21%)239.5 V0.83 V (0.34%)195.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.43 V (0.18%)239.6 V0.71 V (0.3%)167.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.38 V (0.16%)239.6 V0.62 V (0.26%)146.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.3 V (0.13%)239.7 V0.5 V (0.21%)117.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.25 V (0.1%)239.7 V0.41 V (0.17%)97.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.2 V (0.08%)239.8 V0.33 V (0.14%)78.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.15 V (0.06%)239.8 V0.25 V (0.1%)58.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 30 feet one-way at 240V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 0.71V (0.3%) and delivers 239.3V at the load.

What size aluminum wire is required for 225 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 0.83V (0.34%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.