225 Amp Wire Size at 225 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.71%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.15V (17.92%)
Voltage at Load End11.7 VLoss: 0.33 V (73.3 W)
Power & Breaker (125%)2.7 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 225 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A317.51 V (2645.94%)0.0 V523.75 V (4364.56%)71440.2 WDrop/Amp High
12 AWG3.31 mm²20 A199.52 V (1662.7%)0.0 V329.12 V (2742.68%)44893.0 WDrop/Amp High
10 AWG5.26 mm²30 A125.56 V (1046.3%)0.0 V207.11 V (1725.91%)28250.1 WDrop/Amp High
8 AWG8.37 mm²50 A78.9 V (657.53%)0.0 V130.15 V (1084.62%)17753.4 WDrop/Amp High
6 AWG13.3 mm²65 A49.66 V (413.8%)0.0 V81.91 V (682.58%)11172.6 WDrop/Amp High
4 AWG21.15 mm²85 A31.23 V (260.21%)0.0 V51.51 V (429.23%)7025.8 WDrop/Amp High
3 AWG26.67 mm²100 A24.76 V (206.36%)0.0 V40.85 V (340.39%)5571.6 WDrop/Amp High
2 AWG33.62 mm²115 A19.64 V (163.7%)0.0 V32.4 V (270.03%)4419.9 WDrop/Amp High
1 AWG42.41 mm²130 A15.57 V (129.77%)0.0 V25.69 V (214.06%)3503.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.35 V (102.89%)0.0 V20.37 V (169.72%)2778.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.79 V (81.62%)2.2 V16.16 V (134.63%)2203.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.77 V (64.74%)4.2 V12.81 V (106.79%)1748.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.16 V (51.34%)5.8 V10.16 V (84.69%)1386.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.21 V (43.44%)6.8 V8.6 V (71.65%)1172.8 WDrop/Amp High
300 kcmil152.0 mm²285 A4.34 V (36.21%)7.7 V7.17 V (59.73%)977.6 WDrop/Amp High
350 kcmil177.3 mm²310 A3.72 V (31.04%)8.3 V6.14 V (51.2%)838.1 WDrop/Amp High
400 kcmil202.7 mm²335 A3.26 V (27.15%)8.7 V5.37 V (44.79%)733.1 WDrop/Amp High
500 kcmil253.4 mm²380 A2.61 V (21.72%)9.4 V4.3 V (35.83%)586.4 WDrop/Amp High
600 kcmil304.0 mm²420 A2.17 V (18.1%)9.8 V3.58 V (29.86%)488.8 WDrop/Amp High
750 kcmil380.0 mm²475 A1.74 V (14.48%)10.3 V2.87 V (23.89%)391.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.3 V (10.86%)10.7 V2.15 V (17.92%)293.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 225 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 225 feet one-way at 12V (DC), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.33V (2.71%) and delivers 11.7V at the load.

What size aluminum wire is required for 225 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.15V (17.92%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.