🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 800 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.93%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.64V (6.37%)
Voltage at Load End117.7 VLoss: 2.31 V (521.4 W)
Power & Breaker (125%)27.0 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 800 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1128.93 V (940.78%)0.0 V1862.21 V (1551.84%)254009.8 WDrop/Amp High
12 AWG3.31 mm²20 A709.42 V (591.18%)0.0 V1170.21 V (975.18%)159619.4 WDrop/Amp High
10 AWG5.26 mm²30 A446.42 V (372.02%)0.0 V736.39 V (613.66%)100444.9 WDrop/Amp High
8 AWG8.37 mm²50 A280.55 V (233.79%)0.0 V462.77 V (385.64%)63123.1 WDrop/Amp High
6 AWG13.3 mm²65 A176.55 V (147.13%)0.0 V291.23 V (242.69%)39724.8 WDrop/Amp High
4 AWG21.15 mm²85 A111.03 V (92.52%)9.0 V183.14 V (152.62%)24980.6 WDrop/Amp High
3 AWG26.67 mm²100 A88.05 V (73.37%)32.0 V145.23 V (121.03%)19810.3 WDrop/Amp High
2 AWG33.62 mm²115 A69.84 V (58.2%)50.2 V115.21 V (96.01%)15715.1 WDrop/Amp High
1 AWG42.41 mm²130 A55.37 V (46.14%)64.6 V91.33 V (76.11%)12457.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A43.9 V (36.58%)76.1 V72.41 V (60.34%)9877.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A34.82 V (29.02%)85.2 V57.44 V (47.87%)7835.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A27.62 V (23.02%)92.4 V45.56 V (37.97%)6215.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A21.9 V (18.25%)98.1 V36.13 V (30.11%)4928.5 WDrop/Amp High
250 kcmil126.7 mm²255 A18.53 V (15.44%)101.5 V30.57 V (25.48%)4170.0 WDrop/Amp High
300 kcmil152.0 mm²285 A15.45 V (12.87%)104.6 V25.48 V (21.24%)3475.9 WDrop/Amp High
350 kcmil177.3 mm²310 A13.24 V (11.04%)106.8 V21.85 V (18.21%)2979.9 WDrop/Amp High
400 kcmil202.7 mm²335 A11.58 V (9.65%)108.4 V19.11 V (15.92%)2606.5 WDrop/Amp High
500 kcmil253.4 mm²380 A9.27 V (7.72%)110.7 V15.29 V (12.74%)2085.0 WDrop/Amp High
600 kcmil304.0 mm²420 A7.72 V (6.44%)112.3 V12.74 V (10.62%)1738.0 WDrop/Amp High
750 kcmil380.0 mm²475 A6.18 V (5.15%)113.8 V10.19 V (8.49%)1390.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.63 V (3.86%)115.4 V7.64 V (6.37%)1042.7 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 800 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 800 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.31V (1.93%) and delivers 117.7V at the load.

What size aluminum wire is required for 225 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.64V (6.37%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.