🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 800 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.75%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.72V (2.26%)
Voltage at Load End116.7 VLoss: 3.29 V (263.6 W)
Power & Breaker (125%)9.6 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 800 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A401.4 V (334.5%)0.0 V662.12 V (551.77%)32111.9 WDrop/Amp High
12 AWG3.31 mm²20 A252.24 V (210.2%)0.0 V416.08 V (346.73%)20179.0 WDrop/Amp High
10 AWG5.26 mm²30 A158.73 V (132.27%)0.0 V261.83 V (218.19%)12698.2 WDrop/Amp High
8 AWG8.37 mm²50 A99.75 V (83.13%)20.2 V164.54 V (137.12%)7980.0 WDrop/Amp High
6 AWG13.3 mm²65 A62.78 V (52.31%)57.2 V103.55 V (86.29%)5022.0 WDrop/Amp High
4 AWG21.15 mm²85 A39.48 V (32.9%)80.5 V65.12 V (54.26%)3158.0 WDrop/Amp High
3 AWG26.67 mm²100 A31.31 V (26.09%)88.7 V51.64 V (43.03%)2504.4 WDrop/Amp High
2 AWG33.62 mm²115 A24.83 V (20.69%)95.2 V40.96 V (34.14%)1986.7 WDrop/Amp High
1 AWG42.41 mm²130 A19.69 V (16.41%)100.3 V32.47 V (27.06%)1574.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.61 V (13.01%)104.4 V25.75 V (21.46%)1248.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.38 V (10.32%)107.6 V20.42 V (17.02%)990.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.82 V (8.18%)110.2 V16.2 V (13.5%)785.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.79 V (6.49%)112.2 V12.85 V (10.71%)623.1 WDrop/Amp High
250 kcmil126.7 mm²255 A6.59 V (5.49%)113.4 V10.87 V (9.06%)527.2 WDrop/Amp High
300 kcmil152.0 mm²285 A5.49 V (4.58%)114.5 V9.06 V (7.55%)439.4 W~ ≤5%
350 kcmil177.3 mm²310 A4.71 V (3.92%)115.3 V7.77 V (6.47%)376.7 W~ ≤5%
400 kcmil202.7 mm²335 A4.12 V (3.43%)115.9 V6.79 V (5.66%)329.5 W~ ≤5%
500 kcmil253.4 mm²380 A3.29 V (2.75%)116.7 V5.43 V (4.53%)263.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.75 V (2.29%)117.3 V4.53 V (3.78%)219.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.2 V (1.83%)117.8 V3.62 V (3.02%)175.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.65 V (1.37%)118.4 V2.72 V (2.26%)131.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 800 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 800 feet one-way at 120V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 3.29V (2.75%) and delivers 116.7V at the load.

What size aluminum wire is required for 80 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.72V (2.26%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.