⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 175 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.25%
Aluminum Wire (≤3% Drop)3 AWGDrop: 3.53V (2.94%)
Voltage at Load End117.3 VLoss: 2.7 V (67.5 W)
Power & Breaker (125%)3.0 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 175 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A27.44 V (22.87%)92.6 V45.26 V (37.72%)686.0 WDrop/Amp High
12 AWG3.31 mm²20 A17.24 V (14.37%)102.8 V28.44 V (23.7%)431.1 WDrop/Amp High
10 AWG5.26 mm²30 A10.85 V (9.04%)109.1 V17.9 V (14.92%)271.3 WDrop/Amp High
8 AWG8.37 mm²50 A6.82 V (5.68%)113.2 V11.25 V (9.37%)170.5 WDrop/Amp High
6 AWG13.3 mm²65 A4.29 V (3.58%)115.7 V7.08 V (5.9%)107.3 W~ ≤5%
4 AWG21.15 mm²85 A2.7 V (2.25%)117.3 V4.45 V (3.71%)67.5 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.14 V (1.78%)117.9 V3.53 V (2.94%)53.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.7 V (1.41%)118.3 V2.8 V (2.33%)42.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.35 V (1.12%)118.7 V2.22 V (1.85%)33.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.07 V (0.89%)118.9 V1.76 V (1.47%)26.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.85 V (0.71%)119.2 V1.4 V (1.16%)21.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.67 V (0.56%)119.3 V1.11 V (0.92%)16.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.53 V (0.44%)119.5 V0.88 V (0.73%)13.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.45 V (0.38%)119.5 V0.74 V (0.62%)11.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.38 V (0.31%)119.6 V0.62 V (0.52%)9.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.32 V (0.27%)119.7 V0.53 V (0.44%)8.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.28 V (0.23%)119.7 V0.46 V (0.39%)7.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.23 V (0.19%)119.8 V0.37 V (0.31%)5.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.19 V (0.16%)119.8 V0.31 V (0.26%)4.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.15 V (0.13%)119.8 V0.25 V (0.21%)3.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.11 V (0.09%)119.9 V0.19 V (0.15%)2.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 175 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 175 feet one-way at 120V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 2.7V (2.25%) and delivers 117.3V at the load.

What size aluminum wire is required for 25 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 3.53V (2.94%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.