🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 125 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.55%
Aluminum Wire (≤3% Drop)4 AWGDrop: 3.18V (2.65%)
Voltage at Load End116.9 VLoss: 3.07 V (76.6 W)
Power & Breaker (125%)3.0 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 125 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A19.6 V (16.33%)100.4 V32.33 V (26.94%)490.0 WDrop/Amp High
12 AWG3.31 mm²20 A12.32 V (10.26%)107.7 V20.32 V (16.93%)307.9 WDrop/Amp High
10 AWG5.26 mm²30 A7.75 V (6.46%)112.2 V12.78 V (10.65%)193.8 WDrop/Amp High
8 AWG8.37 mm²50 A4.87 V (4.06%)115.1 V8.03 V (6.7%)121.8 W~ ≤5%
6 AWG13.3 mm²65 A3.07 V (2.55%)116.9 V5.06 V (4.21%)76.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.93 V (1.61%)118.1 V3.18 V (2.65%)48.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.53 V (1.27%)118.5 V2.52 V (2.1%)38.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.21 V (1.01%)118.8 V2.0 V (1.67%)30.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.96 V (0.8%)119.0 V1.59 V (1.32%)24.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.76 V (0.64%)119.2 V1.26 V (1.05%)19.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.6 V (0.5%)119.4 V1.0 V (0.83%)15.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.48 V (0.4%)119.5 V0.79 V (0.66%)12.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.38 V (0.32%)119.6 V0.63 V (0.52%)9.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.32 V (0.27%)119.7 V0.53 V (0.44%)8.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.27 V (0.22%)119.7 V0.44 V (0.37%)6.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.23 V (0.19%)119.8 V0.38 V (0.32%)5.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.2 V (0.17%)119.8 V0.33 V (0.28%)5.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.16 V (0.13%)119.8 V0.27 V (0.22%)4.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.13 V (0.11%)119.9 V0.22 V (0.18%)3.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.11 V (0.09%)119.9 V0.18 V (0.15%)2.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.07%)119.9 V0.13 V (0.11%)2.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 125 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 125 feet one-way at 120V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 3.07V (2.55%) and delivers 116.9V at the load.

What size aluminum wire is required for 25 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 3.18V (2.65%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.