🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 75 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)6 AWGDrop: 3.03V (2.53%)
Voltage at Load End117.1 VLoss: 2.92 V (73.1 W)
Power & Breaker (125%)3.0 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 75 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A11.76 V (9.8%)108.2 V19.4 V (16.17%)294.0 WDrop/Amp High
12 AWG3.31 mm²20 A7.39 V (6.16%)112.6 V12.19 V (10.16%)184.7 WDrop/Amp High
10 AWG5.26 mm²30 A4.65 V (3.88%)115.3 V7.67 V (6.39%)116.3 W~ ≤5%
8 AWG8.37 mm²50 A2.92 V (2.44%)117.1 V4.82 V (4.02%)73.1 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.84 V (1.53%)118.2 V3.03 V (2.53%)46.0 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.16 V (0.96%)118.8 V1.91 V (1.59%)28.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.92 V (0.76%)119.1 V1.51 V (1.26%)22.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.73 V (0.61%)119.3 V1.2 V (1.0%)18.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.58 V (0.48%)119.4 V0.95 V (0.79%)14.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.46 V (0.38%)119.5 V0.75 V (0.63%)11.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.36 V (0.3%)119.6 V0.6 V (0.5%)9.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.29 V (0.24%)119.7 V0.47 V (0.4%)7.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.23 V (0.19%)119.8 V0.38 V (0.31%)5.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.19 V (0.16%)119.8 V0.32 V (0.27%)4.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.16 V (0.13%)119.8 V0.27 V (0.22%)4.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.14 V (0.11%)119.9 V0.23 V (0.19%)3.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.12 V (0.1%)119.9 V0.2 V (0.17%)3.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.1 V (0.08%)119.9 V0.16 V (0.13%)2.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.08 V (0.07%)119.9 V0.13 V (0.11%)2.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.06 V (0.05%)119.9 V0.11 V (0.09%)1.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.04%)120.0 V0.08 V (0.07%)1.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 75 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 75 feet one-way at 120V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 2.92V (2.44%) and delivers 117.1V at the load.

What size aluminum wire is required for 25 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 3.03V (2.53%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.