⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 20 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 0.52%
Aluminum Wire (≤3% Drop)10 AWGDrop: 2.05V (0.85%)
Voltage at Load End238.8 VLoss: 1.24 V (31.0 W)
Power & Breaker (125%)6.0 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 20 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3.14 V (1.31%)236.9 V5.17 V (2.16%)78.4 WDrop/Amp High
12 AWG3.31 mm²20 A1.97 V (0.82%)238.0 V3.25 V (1.35%)49.3 WDrop/Amp High
10 AWG5.26 mm²30 A1.24 V (0.52%)238.8 V2.05 V (0.85%)31.0 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A0.78 V (0.32%)239.2 V1.29 V (0.54%)19.5 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A0.49 V (0.2%)239.5 V0.81 V (0.34%)12.3 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.31 V (0.13%)239.7 V0.51 V (0.21%)7.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.24 V (0.1%)239.8 V0.4 V (0.17%)6.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.19 V (0.08%)239.8 V0.32 V (0.13%)4.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.15 V (0.06%)239.8 V0.25 V (0.11%)3.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.12 V (0.05%)239.9 V0.2 V (0.08%)3.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.1 V (0.04%)239.9 V0.16 V (0.07%)2.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.08 V (0.03%)239.9 V0.13 V (0.05%)1.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.06 V (0.03%)239.9 V0.1 V (0.04%)1.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.05 V (0.02%)239.9 V0.08 V (0.04%)1.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.04 V (0.02%)240.0 V0.07 V (0.03%)1.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.04 V (0.02%)240.0 V0.06 V (0.03%)0.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.03 V (0.01%)240.0 V0.05 V (0.02%)0.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.03 V (0.01%)240.0 V0.04 V (0.02%)0.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.02 V (0.01%)240.0 V0.04 V (0.01%)0.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.02 V (0.01%)240.0 V0.03 V (0.01%)0.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.01 V (0.01%)240.0 V0.02 V (0.01%)0.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 20 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 20 feet one-way at 240V (1-Phase), you need 10 AWG copper wire. This produces a voltage drop of 1.24V (0.52%) and delivers 238.8V at the load.

What size aluminum wire is required for 25 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 10 AWG to maintain voltage drop at 2.05V (0.85%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.