🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 125 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.03%
Aluminum Wire (≤3% Drop)6 AWGDrop: 5.06V (2.11%)
Voltage at Load End235.1 VLoss: 4.87 V (121.8 W)
Power & Breaker (125%)6.0 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A19.6 V (8.17%)220.4 V32.33 V (13.47%)490.0 WDrop/Amp High
12 AWG3.31 mm²20 A12.32 V (5.13%)227.7 V20.32 V (8.47%)307.9 WDrop/Amp High
10 AWG5.26 mm²30 A7.75 V (3.23%)232.2 V12.78 V (5.33%)193.8 W~ ≤5%
8 AWG8.37 mm²50 A4.87 V (2.03%)235.1 V8.03 V (3.35%)121.8 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A3.07 V (1.28%)236.9 V5.06 V (2.11%)76.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.93 V (0.8%)238.1 V3.18 V (1.32%)48.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.53 V (0.64%)238.5 V2.52 V (1.05%)38.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.21 V (0.51%)238.8 V2.0 V (0.83%)30.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.96 V (0.4%)239.0 V1.59 V (0.66%)24.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.76 V (0.32%)239.2 V1.26 V (0.52%)19.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.6 V (0.25%)239.4 V1.0 V (0.42%)15.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.48 V (0.2%)239.5 V0.79 V (0.33%)12.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.38 V (0.16%)239.6 V0.63 V (0.26%)9.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.32 V (0.13%)239.7 V0.53 V (0.22%)8.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.27 V (0.11%)239.7 V0.44 V (0.18%)6.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.23 V (0.1%)239.8 V0.38 V (0.16%)5.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.2 V (0.08%)239.8 V0.33 V (0.14%)5.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.16 V (0.07%)239.8 V0.27 V (0.11%)4.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.13 V (0.06%)239.9 V0.22 V (0.09%)3.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.11 V (0.04%)239.9 V0.18 V (0.07%)2.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.03%)239.9 V0.13 V (0.06%)2.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 125 feet one-way at 240V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 4.87V (2.03%) and delivers 235.1V at the load.

What size aluminum wire is required for 25 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 5.06V (2.11%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.