🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 175 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.84%
Aluminum Wire (≤3% Drop)6 AWGDrop: 7.08V (2.95%)
Voltage at Load End233.2 VLoss: 6.82 V (170.5 W)
Power & Breaker (125%)6.0 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A27.44 V (11.43%)212.6 V45.26 V (18.86%)686.0 WDrop/Amp High
12 AWG3.31 mm²20 A17.24 V (7.18%)222.8 V28.44 V (11.85%)431.1 WDrop/Amp High
10 AWG5.26 mm²30 A10.85 V (4.52%)229.1 V17.9 V (7.46%)271.3 W~ ≤5%
8 AWG8.37 mm²50 A6.82 V (2.84%)233.2 V11.25 V (4.69%)170.5 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A4.29 V (1.79%)235.7 V7.08 V (2.95%)107.3 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.7 V (1.12%)237.3 V4.45 V (1.85%)67.5 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.14 V (0.89%)237.9 V3.53 V (1.47%)53.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.7 V (0.71%)238.3 V2.8 V (1.17%)42.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.35 V (0.56%)238.7 V2.22 V (0.92%)33.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.07 V (0.44%)238.9 V1.76 V (0.73%)26.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.85 V (0.35%)239.2 V1.4 V (0.58%)21.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.67 V (0.28%)239.3 V1.11 V (0.46%)16.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.53 V (0.22%)239.5 V0.88 V (0.37%)13.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.45 V (0.19%)239.5 V0.74 V (0.31%)11.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.38 V (0.16%)239.6 V0.62 V (0.26%)9.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.32 V (0.13%)239.7 V0.53 V (0.22%)8.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.28 V (0.12%)239.7 V0.46 V (0.19%)7.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.23 V (0.09%)239.8 V0.37 V (0.15%)5.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.19 V (0.08%)239.8 V0.31 V (0.13%)4.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.15 V (0.06%)239.8 V0.25 V (0.1%)3.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.11 V (0.05%)239.9 V0.19 V (0.08%)2.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 175 feet one-way at 240V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 6.82V (2.84%) and delivers 233.2V at the load.

What size aluminum wire is required for 25 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 7.08V (2.95%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.