🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 500 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.55%
Aluminum Wire (≤3% Drop)1 AWGDrop: 5.49V (2.64%)
Voltage at Load End202.7 VLoss: 5.3 V (229.3 W)
Power & Breaker (125%)9.01 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 500 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A67.89 V (32.64%)140.1 V111.99 V (53.84%)2939.9 WDrop/Amp High
12 AWG3.31 mm²20 A42.66 V (20.51%)165.3 V70.38 V (33.84%)1847.4 WDrop/Amp High
10 AWG5.26 mm²30 A26.85 V (12.91%)181.2 V44.29 V (21.29%)1162.6 WDrop/Amp High
8 AWG8.37 mm²50 A16.87 V (8.11%)191.1 V27.83 V (13.38%)730.6 WDrop/Amp High
6 AWG13.3 mm²65 A10.62 V (5.1%)197.4 V17.51 V (8.42%)459.8 WDrop/Amp High
4 AWG21.15 mm²85 A6.68 V (3.21%)201.3 V11.01 V (5.3%)289.1 W~ ≤5%
3 AWG26.67 mm²100 A5.3 V (2.55%)202.7 V8.73 V (4.2%)229.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A4.2 V (2.02%)203.8 V6.93 V (3.33%)181.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.33 V (1.6%)204.7 V5.49 V (2.64%)144.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.64 V (1.27%)205.4 V4.35 V (2.09%)114.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.09 V (1.01%)205.9 V3.45 V (1.66%)90.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.66 V (0.8%)206.3 V2.74 V (1.32%)71.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.32 V (0.63%)206.7 V2.17 V (1.04%)57.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.11 V (0.54%)206.9 V1.84 V (0.88%)48.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.93 V (0.45%)207.1 V1.53 V (0.74%)40.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.8 V (0.38%)207.2 V1.31 V (0.63%)34.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.7 V (0.33%)207.3 V1.15 V (0.55%)30.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.56 V (0.27%)207.4 V0.92 V (0.44%)24.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.46 V (0.22%)207.5 V0.77 V (0.37%)20.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.37 V (0.18%)207.6 V0.61 V (0.29%)16.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.28 V (0.13%)207.7 V0.46 V (0.22%)12.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 500 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 500 feet one-way at 208V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 5.3V (2.55%) and delivers 202.7V at the load.

What size aluminum wire is required for 25 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 5.49V (2.64%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.