⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 225 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 6.83V (2.84%)
Voltage at Load End234.2 VLoss: 5.79 V (1447.9 W)
Power & Breaker (125%)60.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A352.79 V (147.0%)0.0 V581.94 V (242.48%)88197.8 WDrop/Amp High
12 AWG3.31 mm²20 A221.69 V (92.37%)18.3 V365.69 V (152.37%)55423.4 WDrop/Amp High
10 AWG5.26 mm²30 A139.51 V (58.13%)100.5 V230.12 V (95.88%)34876.7 WDrop/Amp High
8 AWG8.37 mm²50 A87.67 V (36.53%)152.3 V144.62 V (60.26%)21917.7 WDrop/Amp High
6 AWG13.3 mm²65 A55.17 V (22.99%)184.8 V91.01 V (37.92%)13793.3 WDrop/Amp High
4 AWG21.15 mm²85 A34.7 V (14.46%)205.3 V57.23 V (23.85%)8673.8 WDrop/Amp High
3 AWG26.67 mm²100 A27.51 V (11.46%)212.5 V45.39 V (18.91%)6878.6 WDrop/Amp High
2 AWG33.62 mm²115 A21.83 V (9.09%)218.2 V36.0 V (15.0%)5456.6 WDrop/Amp High
1 AWG42.41 mm²130 A17.3 V (7.21%)222.7 V28.54 V (11.89%)4325.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.72 V (5.72%)226.3 V22.63 V (9.43%)3429.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.88 V (4.53%)229.1 V17.95 V (7.48%)2720.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.63 V (3.6%)231.4 V14.24 V (5.93%)2158.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.85 V (2.85%)233.2 V11.29 V (4.7%)1711.3 WDrop/Amp High
250 kcmil126.7 mm²255 A5.79 V (2.41%)234.2 V9.55 V (3.98%)1447.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.83 V (2.01%)235.2 V7.96 V (3.32%)1206.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.14 V (1.72%)235.9 V6.83 V (2.84%)1034.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.62 V (1.51%)236.4 V5.97 V (2.49%)905.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.9 V (1.21%)237.1 V4.78 V (1.99%)724.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.41 V (1.01%)237.6 V3.98 V (1.66%)603.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.93 V (0.8%)238.1 V3.19 V (1.33%)482.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.45 V (0.6%)238.6 V2.39 V (1.0%)362.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 225 feet one-way at 240V (1-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 5.79V (2.41%) and delivers 234.2V at the load.

What size aluminum wire is required for 250 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 6.83V (2.84%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.