🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 250 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 3.54V (2.95%)
Voltage at Load End116.8 VLoss: 3.22 V (804.4 W)
Power & Breaker (125%)30.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 250 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A391.99 V (326.66%)0.0 V646.6 V (538.83%)97997.6 WDrop/Amp High
12 AWG3.31 mm²20 A246.33 V (205.27%)0.0 V406.32 V (338.6%)61581.6 WDrop/Amp High
10 AWG5.26 mm²30 A155.01 V (129.17%)0.0 V255.69 V (213.08%)38751.9 WDrop/Amp High
8 AWG8.37 mm²50 A97.41 V (81.18%)22.6 V160.68 V (133.9%)24353.0 WDrop/Amp High
6 AWG13.3 mm²65 A61.3 V (51.09%)58.7 V101.12 V (84.27%)15325.9 WDrop/Amp High
4 AWG21.15 mm²85 A38.55 V (32.13%)81.4 V63.59 V (52.99%)9637.6 WDrop/Amp High
3 AWG26.67 mm²100 A30.57 V (25.48%)89.4 V50.43 V (42.02%)7642.9 WDrop/Amp High
2 AWG33.62 mm²115 A24.25 V (20.21%)95.7 V40.0 V (33.34%)6062.9 WDrop/Amp High
1 AWG42.41 mm²130 A19.23 V (16.02%)100.8 V31.71 V (26.43%)4806.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.24 V (12.7%)104.8 V25.14 V (20.95%)3810.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.09 V (10.08%)107.9 V19.95 V (16.62%)3022.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.59 V (7.99%)110.4 V15.82 V (13.18%)2397.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.61 V (6.34%)112.4 V12.55 V (10.45%)1901.4 WDrop/Amp High
250 kcmil126.7 mm²255 A6.44 V (5.36%)113.6 V10.62 V (8.85%)1608.8 WDrop/Amp High
300 kcmil152.0 mm²285 A5.36 V (4.47%)114.6 V8.85 V (7.37%)1341.0 W~ ≤5%
350 kcmil177.3 mm²310 A4.6 V (3.83%)115.4 V7.59 V (6.32%)1149.7 W~ ≤5%
400 kcmil202.7 mm²335 A4.02 V (3.35%)116.0 V6.64 V (5.53%)1005.6 W~ ≤5%
500 kcmil253.4 mm²380 A3.22 V (2.68%)116.8 V5.31 V (4.42%)804.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.68 V (2.24%)117.3 V4.42 V (3.69%)670.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.15 V (1.79%)117.9 V3.54 V (2.95%)536.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.61 V (1.34%)118.4 V2.65 V (2.21%)402.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 250 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 250 feet one-way at 120V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 3.22V (2.68%) and delivers 116.8V at the load.

What size aluminum wire is required for 250 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 3.54V (2.95%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.