250 Amp Wire Size at 75 Feet (120V Single-Phase (US Standard Branch))
Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 75 ft (22.9 m) one-way run.
Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 1.61%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 2.28V (1.9%)
Voltage at Load End118.1 VLoss: 1.93 V (482.6 W)
Power & Breaker (125%)30.0 kW350A Breaker Recommended
All AWG & kcmil Wire Gauges for 250 Amps at 75 Feet (120V)
| Wire Gauge | Metric Area | NEC 75°C Cu Ampacity | Copper Voltage Drop | Load Voltage | Aluminum Drop | Line Loss ($I^2R$) | NEC Status |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 mm² | 15 A | 117.6 V (98.0%) | 2.4 V | 193.98 V (161.65%) | 29399.3 W | Drop/Amp High |
| 12 AWG | 3.31 mm² | 20 A | 73.9 V (61.58%) | 46.1 V | 121.9 V (101.58%) | 18474.5 W | Drop/Amp High |
| 10 AWG | 5.26 mm² | 30 A | 46.5 V (38.75%) | 73.5 V | 76.71 V (63.92%) | 11625.6 W | Drop/Amp High |
| 8 AWG | 8.37 mm² | 50 A | 29.22 V (24.35%) | 90.8 V | 48.21 V (40.17%) | 7305.9 W | Drop/Amp High |
| 6 AWG | 13.3 mm² | 65 A | 18.39 V (15.33%) | 101.6 V | 30.34 V (25.28%) | 4597.8 W | Drop/Amp High |
| 4 AWG | 21.15 mm² | 85 A | 11.57 V (9.64%) | 108.4 V | 19.08 V (15.9%) | 2891.3 W | Drop/Amp High |
| 3 AWG | 26.67 mm² | 100 A | 9.17 V (7.64%) | 110.8 V | 15.13 V (12.61%) | 2292.9 W | Drop/Amp High |
| 2 AWG | 33.62 mm² | 115 A | 7.28 V (6.06%) | 112.7 V | 12.0 V (10.0%) | 1818.9 W | Drop/Amp High |
| 1 AWG | 42.41 mm² | 130 A | 5.77 V (4.81%) | 114.2 V | 9.51 V (7.93%) | 1441.9 W | Drop/Amp High |
| 1/0 AWG | 53.49 mm² | 150 A | 4.57 V (3.81%) | 115.4 V | 7.54 V (6.29%) | 1143.2 W | Drop/Amp High |
| 2/0 AWG | 67.43 mm² | 175 A | 3.63 V (3.02%) | 116.4 V | 5.98 V (4.99%) | 906.9 W | Drop/Amp High |
| 3/0 AWG | 85.01 mm² | 200 A | 2.88 V (2.4%) | 117.1 V | 4.75 V (3.96%) | 719.3 W | Drop/Amp High |
| 4/0 AWG | 107.2 mm² | 230 A | 2.28 V (1.9%) | 117.7 V | 3.76 V (3.14%) | 570.4 W | Drop/Amp High |
| 250 kcmil | 126.7 mm² | 255 A | 1.93 V (1.61%) | 118.1 V | 3.18 V (2.65%) | 482.6 W | ✓ PASS (≤3%) |
| 300 kcmil | 152.0 mm² | 285 A | 1.61 V (1.34%) | 118.4 V | 2.65 V (2.21%) | 402.3 W | ✓ PASS (≤3%) |
| 350 kcmil | 177.3 mm² | 310 A | 1.38 V (1.15%) | 118.6 V | 2.28 V (1.9%) | 344.9 W | ✓ PASS (≤3%) |
| 400 kcmil | 202.7 mm² | 335 A | 1.21 V (1.01%) | 118.8 V | 1.99 V (1.66%) | 301.7 W | ✓ PASS (≤3%) |
| 500 kcmil | 253.4 mm² | 380 A | 0.97 V (0.8%) | 119.0 V | 1.59 V (1.33%) | 241.3 W | ✓ PASS (≤3%) |
| 600 kcmil | 304.0 mm² | 420 A | 0.8 V (0.67%) | 119.2 V | 1.33 V (1.11%) | 201.2 W | ✓ PASS (≤3%) |
| 750 kcmil | 380.0 mm² | 475 A | 0.64 V (0.54%) | 119.4 V | 1.06 V (0.88%) | 160.9 W | ✓ PASS (≤3%) |
| 1000 kcmil | 506.7 mm² | 545 A | 0.48 V (0.4%) | 119.5 V | 0.8 V (0.66%) | 120.7 W | ✓ PASS (≤3%) |
Frequently Asked Engineering Questions
What size copper wire do I need for 250 amps at 75 feet (120V)?
To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 75 feet one-way at 120V (1-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 1.93V (1.61%) and delivers 118.1V at the load.
What size aluminum wire is required for 250 amps at 75 feet?
Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 2.28V (1.9%).
What breaker size is needed for a 250A continuous load?
Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.