🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 250 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 1.16%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 6.57V (1.37%)
Voltage at Load End474.4 VLoss: 5.57 V (2413.2 W)
Power & Breaker (125%)207.85 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 250 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A339.47 V (70.72%)140.5 V559.97 V (116.66%)146996.4 WDrop/Amp High
12 AWG3.31 mm²20 A213.32 V (44.44%)266.7 V351.89 V (73.31%)92372.4 WDrop/Amp High
10 AWG5.26 mm²30 A134.24 V (27.97%)345.8 V221.43 V (46.13%)58127.9 WDrop/Amp High
8 AWG8.37 mm²50 A84.36 V (17.58%)395.6 V139.16 V (28.99%)36529.6 WDrop/Amp High
6 AWG13.3 mm²65 A53.09 V (11.06%)426.9 V87.57 V (18.24%)22988.9 WDrop/Amp High
4 AWG21.15 mm²85 A33.39 V (6.96%)446.6 V55.07 V (11.47%)14456.4 WDrop/Amp High
3 AWG26.67 mm²100 A26.48 V (5.52%)453.5 V43.67 V (9.1%)11464.3 WDrop/Amp High
2 AWG33.62 mm²115 A21.0 V (4.38%)459.0 V34.64 V (7.22%)9094.4 WDrop/Amp High
1 AWG42.41 mm²130 A16.65 V (3.47%)463.4 V27.46 V (5.72%)7209.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.2 V (2.75%)466.8 V21.77 V (4.54%)5716.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.47 V (2.18%)469.5 V17.27 V (3.6%)4534.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.31 V (1.73%)471.7 V13.7 V (2.85%)3596.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.59 V (1.37%)473.4 V10.87 V (2.26%)2852.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.57 V (1.16%)474.4 V9.19 V (1.92%)2413.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.65 V (0.97%)475.4 V7.66 V (1.6%)2011.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.98 V (0.83%)476.0 V6.57 V (1.37%)1724.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.48 V (0.73%)476.5 V5.75 V (1.2%)1508.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.79 V (0.58%)477.2 V4.6 V (0.96%)1206.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.32 V (0.48%)477.7 V3.83 V (0.8%)1005.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.86 V (0.39%)478.1 V3.07 V (0.64%)804.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.39 V (0.29%)478.6 V2.3 V (0.48%)603.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 250 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 250 feet one-way at 480V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 5.57V (1.16%) and delivers 474.4V at the load.

What size aluminum wire is required for 250 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 6.57V (1.37%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.