🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 275 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.92V (2.43%)
Voltage at Load End116.5 VLoss: 3.54 V (884.8 W)
Power & Breaker (125%)30.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 275 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A431.19 V (359.32%)0.0 V711.26 V (592.72%)107797.4 WDrop/Amp High
12 AWG3.31 mm²20 A270.96 V (225.8%)0.0 V446.96 V (372.46%)67739.7 WDrop/Amp High
10 AWG5.26 mm²30 A170.51 V (142.09%)0.0 V281.26 V (234.38%)42627.1 WDrop/Amp High
8 AWG8.37 mm²50 A107.15 V (89.29%)12.8 V176.75 V (147.29%)26788.4 WDrop/Amp High
6 AWG13.3 mm²65 A67.43 V (56.2%)52.6 V111.23 V (92.7%)16858.5 WDrop/Amp High
4 AWG21.15 mm²85 A42.41 V (35.34%)77.6 V69.95 V (58.29%)10601.3 WDrop/Amp High
3 AWG26.67 mm²100 A33.63 V (28.02%)86.4 V55.47 V (46.23%)8407.1 WDrop/Amp High
2 AWG33.62 mm²115 A26.68 V (22.23%)93.3 V44.0 V (36.67%)6669.2 WDrop/Amp High
1 AWG42.41 mm²130 A21.15 V (17.62%)98.9 V34.88 V (29.07%)5286.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A16.77 V (13.97%)103.2 V27.66 V (23.05%)4191.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.3 V (11.08%)106.7 V21.94 V (18.28%)3325.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.55 V (8.79%)109.4 V17.4 V (14.5%)2637.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.37 V (6.97%)111.6 V13.8 V (11.5%)2091.6 WDrop/Amp High
250 kcmil126.7 mm²255 A7.08 V (5.9%)112.9 V11.68 V (9.73%)1769.7 WDrop/Amp High
300 kcmil152.0 mm²285 A5.9 V (4.92%)114.1 V9.73 V (8.11%)1475.1 W~ ≤5%
350 kcmil177.3 mm²310 A5.06 V (4.22%)114.9 V8.34 V (6.95%)1264.6 W~ ≤5%
400 kcmil202.7 mm²335 A4.42 V (3.69%)115.6 V7.3 V (6.08%)1106.2 W~ ≤5%
500 kcmil253.4 mm²380 A3.54 V (2.95%)116.5 V5.84 V (4.87%)884.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.95 V (2.46%)117.0 V4.87 V (4.06%)737.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.36 V (1.97%)117.6 V3.89 V (3.24%)590.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.77 V (1.48%)118.2 V2.92 V (2.43%)442.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 275 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 275 feet one-way at 120V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 3.54V (2.95%) and delivers 116.5V at the load.

What size aluminum wire is required for 250 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.92V (2.43%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.