🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 500 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)9× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.98%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.31V (44.24%)
Voltage at Load End11.6 VLoss: 0.36 V (89.4 W)
Power & Breaker (125%)3.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 500 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A783.98 V (6533.17%)0.0 V1293.2 V (10776.68%)195995.2 WDrop/Amp High
12 AWG3.31 mm²20 A492.65 V (4105.44%)0.0 V812.65 V (6772.05%)123163.1 WDrop/Amp High
10 AWG5.26 mm²30 A310.02 V (2583.46%)0.0 V511.38 V (4261.5%)77503.8 WDrop/Amp High
8 AWG8.37 mm²50 A194.82 V (1623.54%)0.0 V321.37 V (2678.08%)48706.1 WDrop/Amp High
6 AWG13.3 mm²65 A122.61 V (1021.73%)0.0 V202.25 V (1685.38%)30651.9 WDrop/Amp High
4 AWG21.15 mm²85 A77.1 V (642.51%)0.0 V127.18 V (1059.83%)19275.2 WDrop/Amp High
3 AWG26.67 mm²100 A61.14 V (509.52%)0.0 V100.86 V (840.48%)15285.7 WDrop/Amp High
2 AWG33.62 mm²115 A48.5 V (404.19%)0.0 V80.01 V (666.73%)12125.8 WDrop/Amp High
1 AWG42.41 mm²130 A38.45 V (320.42%)0.0 V63.43 V (528.54%)9612.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A30.49 V (254.05%)0.0 V50.29 V (419.06%)7621.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A24.18 V (201.53%)0.0 V39.89 V (332.43%)6045.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.18 V (159.85%)0.0 V31.64 V (263.68%)4795.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.21 V (126.76%)0.0 V25.09 V (209.1%)3802.9 WDrop/Amp High
250 kcmil126.7 mm²255 A12.87 V (107.25%)0.0 V21.23 V (176.92%)3217.6 WDrop/Amp High
300 kcmil152.0 mm²285 A10.73 V (89.4%)1.3 V17.7 V (147.47%)2682.0 WDrop/Amp High
350 kcmil177.3 mm²310 A9.2 V (76.64%)2.8 V15.17 V (126.43%)2299.3 WDrop/Amp High
400 kcmil202.7 mm²335 A8.04 V (67.04%)4.0 V13.27 V (110.58%)2011.2 WDrop/Amp High
500 kcmil253.4 mm²380 A6.44 V (53.63%)5.6 V10.62 V (88.46%)1608.8 WDrop/Amp High
600 kcmil304.0 mm²420 A5.36 V (44.7%)6.6 V8.85 V (73.74%)1341.0 WDrop/Amp High
750 kcmil380.0 mm²475 A4.29 V (35.76%)7.7 V7.08 V (58.99%)1072.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.22 V (26.82%)8.8 V5.31 V (44.24%)804.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 500 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 500 feet one-way at 12V (DC), you need 9× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.36V (2.98%) and delivers 11.6V at the load.

What size aluminum wire is required for 250 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.31V (44.24%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.