⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 500 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.65V (22.12%)
Voltage at Load End11.7 VLoss: 0.32 V (40.2 W)
Power & Breaker (125%)1.5 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 500 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A391.99 V (3266.59%)0.0 V646.6 V (5388.34%)48998.8 WDrop/Amp High
12 AWG3.31 mm²20 A246.33 V (2052.72%)0.0 V406.32 V (3386.03%)30790.8 WDrop/Amp High
10 AWG5.26 mm²30 A155.01 V (1291.73%)0.0 V255.69 V (2130.75%)19376.0 WDrop/Amp High
8 AWG8.37 mm²50 A97.41 V (811.77%)0.0 V160.68 V (1339.04%)12176.5 WDrop/Amp High
6 AWG13.3 mm²65 A61.3 V (510.86%)0.0 V101.12 V (842.69%)7663.0 WDrop/Amp High
4 AWG21.15 mm²85 A38.55 V (321.25%)0.0 V63.59 V (529.92%)4818.8 WDrop/Amp High
3 AWG26.67 mm²100 A30.57 V (254.76%)0.0 V50.43 V (420.24%)3821.4 WDrop/Amp High
2 AWG33.62 mm²115 A24.25 V (202.1%)0.0 V40.0 V (333.37%)3031.5 WDrop/Amp High
1 AWG42.41 mm²130 A19.23 V (160.21%)0.0 V31.71 V (264.27%)2403.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.24 V (127.02%)0.0 V25.14 V (209.53%)1905.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.09 V (100.76%)0.0 V19.95 V (166.21%)1511.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.59 V (79.93%)2.4 V15.82 V (131.84%)1198.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.61 V (63.38%)4.4 V12.55 V (104.55%)950.7 WDrop/Amp High
250 kcmil126.7 mm²255 A6.44 V (53.63%)5.6 V10.62 V (88.46%)804.4 WDrop/Amp High
300 kcmil152.0 mm²285 A5.36 V (44.7%)6.6 V8.85 V (73.74%)670.5 WDrop/Amp High
350 kcmil177.3 mm²310 A4.6 V (38.32%)7.4 V7.59 V (63.21%)574.8 WDrop/Amp High
400 kcmil202.7 mm²335 A4.02 V (33.52%)8.0 V6.64 V (55.29%)502.8 WDrop/Amp High
500 kcmil253.4 mm²380 A3.22 V (26.81%)8.8 V5.31 V (44.23%)402.2 WDrop/Amp High
600 kcmil304.0 mm²420 A2.68 V (22.35%)9.3 V4.42 V (36.87%)335.3 WDrop/Amp High
750 kcmil380.0 mm²475 A2.15 V (17.88%)9.9 V3.54 V (29.49%)268.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.61 V (13.41%)10.4 V2.65 V (22.12%)201.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 500 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 500 feet one-way at 12V (DC), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.32V (2.68%) and delivers 11.7V at the load.

What size aluminum wire is required for 125 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.65V (22.12%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.