🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 600 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.37V (2.65%)
Voltage at Load End233.6 VLoss: 6.44 V (1609.2 W)
Power & Breaker (125%)60.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A940.78 V (391.99%)0.0 V1551.84 V (646.6%)235194.2 WDrop/Amp High
12 AWG3.31 mm²20 A591.18 V (246.33%)0.0 V975.18 V (406.32%)147795.8 WDrop/Amp High
10 AWG5.26 mm²30 A372.02 V (155.01%)0.0 V613.66 V (255.69%)93004.6 WDrop/Amp High
8 AWG8.37 mm²50 A233.79 V (97.41%)6.2 V385.64 V (160.68%)58447.3 WDrop/Amp High
6 AWG13.3 mm²65 A147.13 V (61.3%)92.9 V242.69 V (101.12%)36782.3 WDrop/Amp High
4 AWG21.15 mm²85 A92.52 V (38.55%)147.5 V152.62 V (63.59%)23130.2 WDrop/Amp High
3 AWG26.67 mm²100 A73.37 V (30.57%)166.6 V121.03 V (50.43%)18342.9 WDrop/Amp High
2 AWG33.62 mm²115 A58.2 V (24.25%)181.8 V96.01 V (40.0%)14551.0 WDrop/Amp High
1 AWG42.41 mm²130 A46.14 V (19.23%)193.9 V76.11 V (31.71%)11535.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A36.58 V (15.24%)203.4 V60.34 V (25.14%)9145.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A29.02 V (12.09%)211.0 V47.87 V (19.95%)7255.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A23.02 V (9.59%)217.0 V37.97 V (15.82%)5754.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A18.25 V (7.61%)221.7 V30.11 V (12.55%)4563.5 WDrop/Amp High
250 kcmil126.7 mm²255 A15.44 V (6.44%)224.6 V25.48 V (10.62%)3861.1 WDrop/Amp High
300 kcmil152.0 mm²285 A12.87 V (5.36%)227.1 V21.24 V (8.85%)3218.4 WDrop/Amp High
350 kcmil177.3 mm²310 A11.04 V (4.6%)229.0 V18.21 V (7.59%)2759.2 W~ ≤5%
400 kcmil202.7 mm²335 A9.65 V (4.02%)230.3 V15.92 V (6.64%)2413.4 W~ ≤5%
500 kcmil253.4 mm²380 A7.72 V (3.22%)232.3 V12.74 V (5.31%)1930.6 W~ ≤5%
600 kcmil304.0 mm²420 A6.44 V (2.68%)233.6 V10.62 V (4.42%)1609.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A5.15 V (2.15%)234.9 V8.49 V (3.54%)1287.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.86 V (1.61%)236.1 V6.37 V (2.65%)965.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 600 feet one-way at 240V (1-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 6.44V (2.68%) and delivers 233.6V at the load.

What size aluminum wire is required for 250 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.37V (2.65%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.