🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 225 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 1.92%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 4.55V (1.9%)
Voltage at Load End235.4 VLoss: 4.6 V (2190.6 W)
Power & Breaker (125%)114.32 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A336.08 V (140.03%)0.0 V554.37 V (230.99%)160079.1 WDrop/Amp High
12 AWG3.31 mm²20 A211.19 V (88.0%)28.8 V348.37 V (145.15%)100593.5 WDrop/Amp High
10 AWG5.26 mm²30 A132.9 V (55.37%)107.1 V219.22 V (91.34%)63301.2 WDrop/Amp High
8 AWG8.37 mm²50 A83.52 V (34.8%)156.5 V137.77 V (57.4%)39780.7 WDrop/Amp High
6 AWG13.3 mm²65 A52.56 V (21.9%)187.4 V86.7 V (36.12%)25034.9 WDrop/Amp High
4 AWG21.15 mm²85 A33.05 V (13.77%)206.9 V54.52 V (22.72%)15743.0 WDrop/Amp High
3 AWG26.67 mm²100 A26.21 V (10.92%)213.8 V43.24 V (18.01%)12484.6 WDrop/Amp High
2 AWG33.62 mm²115 A20.79 V (8.66%)219.2 V34.3 V (14.29%)9903.8 WDrop/Amp High
1 AWG42.41 mm²130 A16.48 V (6.87%)223.5 V27.19 V (11.33%)7851.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.07 V (5.45%)226.9 V21.56 V (8.98%)6224.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.37 V (4.32%)229.6 V17.1 V (7.13%)4937.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.22 V (3.43%)231.8 V13.56 V (5.65%)3916.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.52 V (2.72%)233.5 V10.76 V (4.48%)3106.0 WDrop/Amp High
250 kcmil126.7 mm²255 A5.52 V (2.3%)234.5 V9.1 V (3.79%)2628.0 WDrop/Amp High
300 kcmil152.0 mm²285 A4.6 V (1.92%)235.4 V7.59 V (3.16%)2190.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.94 V (1.64%)236.1 V6.5 V (2.71%)1878.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.45 V (1.44%)236.6 V5.69 V (2.37%)1642.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.76 V (1.15%)237.2 V4.55 V (1.9%)1314.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.3 V (0.96%)237.7 V3.79 V (1.58%)1095.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.84 V (0.77%)238.2 V3.03 V (1.26%)876.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.38 V (0.57%)238.6 V2.28 V (0.95%)657.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 225 feet one-way at 240V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 4.6V (1.92%) and delivers 235.4V at the load.

What size aluminum wire is required for 275 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 4.55V (1.9%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.