🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 275 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.7%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.21V (2.68%)
Voltage at Load End116.8 VLoss: 3.25 V (892.4 W)
Power & Breaker (125%)33.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 275 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A474.31 V (395.26%)0.0 V782.39 V (651.99%)130434.8 WDrop/Amp High
12 AWG3.31 mm²20 A298.05 V (248.38%)0.0 V491.65 V (409.71%)81965.1 WDrop/Amp High
10 AWG5.26 mm²30 A187.56 V (156.3%)0.0 V309.39 V (257.82%)51578.8 WDrop/Amp High
8 AWG8.37 mm²50 A117.87 V (98.22%)2.1 V194.43 V (162.02%)32413.9 WDrop/Amp High
6 AWG13.3 mm²65 A74.18 V (61.81%)45.8 V122.36 V (101.97%)20398.8 WDrop/Amp High
4 AWG21.15 mm²85 A46.65 V (38.87%)73.4 V76.94 V (64.12%)12827.6 WDrop/Amp High
3 AWG26.67 mm²100 A36.99 V (30.83%)83.0 V61.02 V (50.85%)10172.6 WDrop/Amp High
2 AWG33.62 mm²115 A29.34 V (24.45%)90.7 V48.4 V (40.34%)8069.7 WDrop/Amp High
1 AWG42.41 mm²130 A23.26 V (19.39%)96.7 V38.37 V (31.98%)6397.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A18.44 V (15.37%)101.6 V30.42 V (25.35%)5072.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A14.63 V (12.19%)105.4 V24.13 V (20.11%)4023.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.61 V (9.67%)108.4 V19.14 V (15.95%)3191.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.2 V (7.67%)110.8 V15.18 V (12.65%)2530.8 WDrop/Amp High
250 kcmil126.7 mm²255 A7.79 V (6.49%)112.2 V12.84 V (10.7%)2141.3 WDrop/Amp High
300 kcmil152.0 mm²285 A6.49 V (5.41%)113.5 V10.71 V (8.92%)1784.9 WDrop/Amp High
350 kcmil177.3 mm²310 A5.56 V (4.64%)114.4 V9.18 V (7.65%)1530.2 W~ ≤5%
400 kcmil202.7 mm²335 A4.87 V (4.06%)115.1 V8.03 V (6.69%)1338.5 W~ ≤5%
500 kcmil253.4 mm²380 A3.89 V (3.24%)116.1 V6.42 V (5.35%)1070.7 W~ ≤5%
600 kcmil304.0 mm²420 A3.25 V (2.7%)116.8 V5.35 V (4.46%)892.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.6 V (2.16%)117.4 V4.28 V (3.57%)714.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.95 V (1.62%)118.1 V3.21 V (2.68%)535.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 275 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 275 feet one-way at 120V (1-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 3.25V (2.7%) and delivers 116.8V at the load.

What size aluminum wire is required for 275 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.21V (2.68%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.