🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 300 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 6.07V (2.92%)
Voltage at Load End201.9 VLoss: 6.13 V (2920.7 W)
Power & Breaker (125%)99.07 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 300 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A448.11 V (215.44%)0.0 V739.16 V (355.37%)213438.8 WDrop/Amp High
12 AWG3.31 mm²20 A281.59 V (135.38%)0.0 V464.49 V (223.31%)134124.7 WDrop/Amp High
10 AWG5.26 mm²30 A177.2 V (85.19%)30.8 V292.29 V (140.53%)84401.6 WDrop/Amp High
8 AWG8.37 mm²50 A111.36 V (53.54%)96.6 V183.69 V (88.31%)53040.9 WDrop/Amp High
6 AWG13.3 mm²65 A70.08 V (33.69%)137.9 V115.6 V (55.58%)33379.9 WDrop/Amp High
4 AWG21.15 mm²85 A44.07 V (21.19%)163.9 V72.69 V (34.95%)20990.7 WDrop/Amp High
3 AWG26.67 mm²100 A34.95 V (16.8%)173.1 V57.65 V (27.72%)16646.1 WDrop/Amp High
2 AWG33.62 mm²115 A27.72 V (13.33%)180.3 V45.73 V (21.99%)13205.0 WDrop/Amp High
1 AWG42.41 mm²130 A21.98 V (10.57%)186.0 V36.25 V (17.43%)10468.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.42 V (8.38%)190.6 V28.74 V (13.82%)8299.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.82 V (6.65%)194.2 V22.8 V (10.96%)6583.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.96 V (5.27%)197.0 V18.09 V (8.7%)5222.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.69 V (4.18%)199.3 V14.34 V (6.9%)4141.3 WDrop/Amp High
250 kcmil126.7 mm²255 A7.36 V (3.54%)200.6 V12.13 V (5.83%)3504.0 WDrop/Amp High
300 kcmil152.0 mm²285 A6.13 V (2.95%)201.9 V10.11 V (4.86%)2920.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A5.26 V (2.53%)202.7 V8.67 V (4.17%)2504.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.6 V (2.21%)203.4 V7.58 V (3.65%)2190.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.68 V (1.77%)204.3 V6.07 V (2.92%)1752.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.07 V (1.47%)204.9 V5.06 V (2.43%)1460.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.45 V (1.18%)205.5 V4.05 V (1.95%)1168.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.84 V (0.88%)206.2 V3.03 V (1.46%)876.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 300 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 300 feet one-way at 208V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 6.13V (2.95%) and delivers 201.9V at the load.

What size aluminum wire is required for 275 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 6.07V (2.92%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.