⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 350 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 5.9V (2.84%)
Voltage at Load End201.9 VLoss: 6.13 V (2921.3 W)
Power & Breaker (125%)99.07 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 350 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A522.79 V (251.34%)0.0 V862.36 V (414.6%)249011.9 WDrop/Amp High
12 AWG3.31 mm²20 A328.52 V (157.94%)0.0 V541.9 V (260.53%)156478.8 WDrop/Amp High
10 AWG5.26 mm²30 A206.73 V (99.39%)1.3 V341.01 V (163.95%)98468.6 WDrop/Amp High
8 AWG8.37 mm²50 A129.92 V (62.46%)78.1 V214.3 V (103.03%)61881.1 WDrop/Amp High
6 AWG13.3 mm²65 A81.76 V (39.31%)126.2 V134.87 V (64.84%)38943.2 WDrop/Amp High
4 AWG21.15 mm²85 A51.41 V (24.72%)156.6 V84.81 V (40.77%)24489.1 WDrop/Amp High
3 AWG26.67 mm²100 A40.77 V (19.6%)167.2 V67.26 V (32.33%)19420.5 WDrop/Amp High
2 AWG33.62 mm²115 A32.34 V (15.55%)175.7 V53.35 V (25.65%)15405.9 WDrop/Amp High
1 AWG42.41 mm²130 A25.64 V (12.33%)182.4 V42.29 V (20.33%)12212.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.33 V (9.77%)187.7 V33.53 V (16.12%)9683.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.13 V (7.75%)191.9 V26.6 V (12.79%)7681.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.79 V (6.15%)195.2 V21.1 V (10.14%)6092.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.14 V (4.88%)197.9 V16.73 V (8.04%)4831.6 WDrop/Amp High
250 kcmil126.7 mm²255 A8.58 V (4.13%)199.4 V14.16 V (6.81%)4088.0 WDrop/Amp High
300 kcmil152.0 mm²285 A7.15 V (3.44%)200.8 V11.8 V (5.67%)3407.5 W~ ≤5%
350 kcmil177.3 mm²310 A6.13 V (2.95%)201.9 V10.12 V (4.86%)2921.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A5.36 V (2.58%)202.6 V8.85 V (4.25%)2555.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A4.29 V (2.06%)203.7 V7.08 V (3.4%)2044.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.58 V (1.72%)204.4 V5.9 V (2.84%)1703.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.86 V (1.38%)205.1 V4.72 V (2.27%)1363.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.15 V (1.03%)205.9 V3.54 V (1.7%)1022.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 350 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 350 feet one-way at 208V (3-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 6.13V (2.95%) and delivers 201.9V at the load.

What size aluminum wire is required for 275 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 5.9V (2.84%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.